ED34-862 Fan Performances
FXMQ-P 265
7
FXMQ100PVE
FXMQ125PVE
250
25 25
Upper limit of ESP
(NOTE 8)
200
2020
Upper limit
of ESP by
airflow auto
adjustment
150
1515
"HH"
100
1010
"H"
External static pressure
Lower limit
of ESP by
airflow auto
adjustment
"L"
50
55
Lower limit of ESP
000
363026 28242220 32 34 37
(mmH
2O) (Pa) (mmH2O)
Air flow (m
3
/min)(mmH2O) (Pa) (mmH2O)
Notes:
1. As for this machine, less than 10% of the volume of
blow-off air is automatically adjusted to the rated
quantity by airflow auto adjustment at the time of
installation.
2. After duct construction completion, please perform
local setting "airflow auto adjustment" by remote
controller.
3. About the local setting method of the "airflow auto
adjustment", look at the installation manual which is
attached to an indoor unit.
4. External static pressure that can adjust by "airflow
auto adjustment" function is 50Pa - 200Pa (When
air flow is HH).
5. It is not operated auto adjustment, operated in air
flow that is different from rated quantity in the case
of use out of external static pressure range
mentioned above.
6. This figure shows a fan characteristics at the time of
"HH" "H" and "L".
7. The remote controller can be used to change "HH"
"H" and "L".
8. ESP : external static pressure.
9. Please set the external static pressure of the
suction duct at 150Pa or less.
3D060581A
250
25 25
Upper limit
of ESP by
airflow auto
adjustment
Upper limit of ESP
(NOTE 8)
200
2020
150
15 15
"HH"
100
1010
"H"
External static pressure
"L"
Lower limit
of ESP by
airflow auto
adjustment
50
55
Lower limit of ESP
00 0
25 27 29 4123 33 37 39 433531
(mmH
2O) (Pa) (mmH2O)
Air flow (m
3
/min)(mmH2O) (mmH2O)
Notes:
1. As for this machine, less than 10% of the volume of
blow-off air is automatically adjusted to the rated
quantity by airflow auto adjustment at the time of
installation.
2. After duct construction completion, please perform
local setting "airflow auto adjustment" by remote
controller.
3. About the local setting method of the "airflow auto
adjustment", look at the installation manual which is
attached to an indoor unit.
4. External static pressure that can adjust by "airflow
auto adjustment" function is 50Pa - 200Pa (When
air flow is HH).
5. It is not operated auto adjustment, operated in air
flow that is different from rated quantity in the case
of use out of external static pressure range
mentioned above.
6. This figure shows a fan characteristics at the time
of "HH" "H" and "L".
7. The remote controller can be used to change "HH"
"H" and "L".
8. ESP : external static pressure.
9. Please set the external static pressure of the
suction duct at 150Pa or less.
3D060582A