Fan Performances ED34-862
264 FXMQ-P
FXMQ63PVE
FXMQ80PVE
16 201815 1914 2117 22 2313
00 0
Lower limit of ESP
55
50
Lower limit
of ESP by
airflow auto
adjustment
"L"
External static pressure
"H"
10 10
100
"HH"
1515
150
Upper limit
of ESP by
airflow auto
adjustment
20 20
200
Upper limit of ESP
(NOTE 8)
2525
250
(mmH
2O) (Pa) (mmH2O)
Air flow (m
3
/min)(mmH2O) (Pa) (mmH2O)
Notes:
1. As for this machine, less than 10% of the volume of
blow-off air is automatically adjusted to the rated
quantity by airflow auto adjustment at the time of
installation.
2. After duct construction completion, please perform
local setting "airflow auto adjustment" by remote
controller.
3. About the local setting method of the "airflow auto
adjustment", look at the installation manual which is
attached to an indoor unit.
4. External static pressure that can adjust by "airflow
auto adjustment" function is 50Pa - 200Pa (When
air flow is HH).
5. It is not operated auto adjustment, operated in air
flow that is different from rated quantity in the case
of use out of external static pressure range
mentioned above.
6. This figure shows a fan characteristics at the time
of "HH" "H" and "L".
7. The remote controller can be used to change "HH"
"H" and "L".
8. ESP : external static pressure.
9. Please set the external static pressure of the
suction duct at 150Pa or less.
3D060579A
17 28272118 19 262322 2520 24
00 0
Lower limit of ESP
55
50
Lower limit
of ESP by
airflow auto
adjustment
External static pressure
"L"
10 10
100
"H"
"HH"
1515
150
Upper limit
of ESP by
airflow auto
adjustment
20 20
200
Upper limit of ESP
(NOTE 8)
25 25
250
(mmH
2O) (Pa) (mmH2O)
Air flow (m
3
/min)(mmH2O) (mmH2O)
Notes:
1. As for this machine, less than 10% of the volume of
blow-off air is automatically adjusted to the rated
quantity by airflow auto adjustment at the time of
installation.
2. After duct construction completion, please perform
local setting "airflow auto adjustment" by remote
controller.
3. About the local setting method of the "airflow auto
adjustment", look at the installation manual which is
attached to an indoor unit.
4. External static pressure that can adjust by "airflow
auto adjustment" function is 50Pa - 200Pa (When
air flow is HH).
5. It is not operated auto adjustment, operated in air
flow that is different from rated quantity in the case
of use out of external static pressure range
mentioned above.
6. This figure shows a fan characteristics at the time of
"HH" "H" and "L".
7. The remote controller can be used to change "HH"
"H" and "L".
8. ESP : external static pressure.
9. Please set the external static pressure of the
suction duct at 150Pa or less.
3D060580A