Capacity Tables ED34-862
428 FXMQ-MF
FXMQ200MFV1
Cooling
Notes
1. The above capacities are based on the following conditions:
Air discharge temperature setting: 18°C for cooling operation (Factory setting).
Equivalent piping length: 7.5m
Level difference: 0m
2. The above capacities values are general average values which can be generated by each compressor operation level.
3. A value enclosed in means rated capacity.
4D046309
Outdoor temperature °C WB
°C DB
15.0 17.0 20.0 23.0 26.0 28.0 30.0 32.0
Capacity
kW kW kW kW kW kW kW kW
20.0 5.7 6.1 - - - - - -
22.0 5.7 6.1 8.2 - - - - -
25.0 5.7 6.1 8.2 10.8 - - - -
27.0 - 6.1 8.1 10.7 - - - -
29.0 - - 8.1 10.6 17.6 - - -
31.0 - - 8.0 10.5 17.4 22.6 - -
33.0 - - 8.0 10.3 17.3 22.4 26.2 -
35.0 - - - 10.2 17.1 22.2 26.1 27.8