ED34-862 Capacity Tables
FXMQ-MF 429
13
FXMQ250MFV1
Cooling
Notes
1. The above capacities are based on the following conditions:
Air discharge temperature setting: 18°C for cooling operation (Factory setting).
Equivalent piping length: 7.5m
Level difference: 0m
2. The above capacities values are general average values which can be generated by each compressor operation level.
3. A value enclosed in means rated capacity.
4D046310
Outdoor temperature °C WB
°C DB
15.0 17.0 20.0 23.0 26.0 28.0 30.0 32.0
Capacity
kW kW kW kW kW kW kW kW
20.0 7.1 7.6 - - - - - -
22.0 7.1 7.6 10.2 - - - - -
25.0 7.1 7.6 10.2 13.5 - - - -
27.0 - 7.6 10.1 13.4 - - - -
29.0 - - 10.1 13.3 22.0 - - -
31.0 - - 10.0 13.1 21.8 28.2 - -
33.0 - - 10.0 12.9 21.6 28.0 32.8 -
35.0 - - - 12.8 21.4 27.8 32.6 34.8