LED Display and Error Description
Power / Operation LED light (both green)
Power LED Off, Operation LED On
Power LED On, Operation LED Off
For all units - Operation LED light (Green)
Electrical heater failure
Green LED blinks 1
times, stops for 3s
Only for unit with EH.
EH safety switch is open.
1. Change fan speed to high.
2. Replace the damaged EH safety switch.
Indoor coil sensor 2
failure
Green LED blinks 2
times, stops for 3s
Ti2 sensor unplugged or
damaged.
1. Check if Ti2 plug is connected or not.
2. Check if sensor’s resistance is correct or
not.
Return air sensor failure
Green LED blinks 3
times, stops for 3s
Room sensor unplugged
or damaged.
1. Check if Tr plug is connected or not.
2. Check if sensor’s resistance is correct or
not.
Indoor coil sensor 1
failure
Green LED blinks 4
times, stops for 3s
Ti1 sensor unplugged or
damaged.
1. Check if Ti1 plug is connected or not.
2. Check if sensor’s resistance is correct or
not.
Indoor coil low
temperature protection
Green LED blinks 5
times, stops for 3s
Water temperature is
lower than 3ºC.
Check the water temperature.
Indoor coil over heat
protection
Green LED blinks 6
times, stops for 3s
Water temperature is
higher than 70ºC.
Check the water temperature
Green LED blinks 9
times, stops for 3s
1. Check DIPB-SW5 and SW6 setting.
2. Check the EC motor.
Green LED blinks 11
times, stops for 3s
When unit is standby,
Tr<2ºC.
1. Turn on unit to keep Tr higher than 5ºC