The LCP indicates (with a wrench-icon and an “M”) when it is time for a Preventive Maintenance Action, and can be programmed to be indicated on a
digital output in parameter group 5-3*. The Preventive Maintenance Status may be read in par.16-96
Maintenance Word
. A Preventive Maintenance
indication can be reset from a digital input, the FC bus or manually from the LCP through par.23-15
Reset Maintenance Word
.
A Maintenance Log with the latest 10 loggings can be read from parameter group 18-0* and via the Alarm log button on the LCP after selecting Maintenance
Log.
NB!
The Preventive Maintenance Events are defined in a 20 element array. Hence each Preventive Maintenance Event must use the same
array element index in par.23-10
Maintenance Item
to par.23-14
Maintenance Date and Time
.
23-10 Maintenance Item
Option: Function:
Array with 20 elements displayed below parameter number in the display. Press [OK] and step
between elements by means of and buttons on the LCP.
Select the item to be associated with the Preventive Maintenance Event.
[1] * Motor bearings
[2] Fan bearings
[3] Pump bearings
[4] Valve
[5] Pressure transmitter
[6] Flow transmitter
[7] Temperature transm.
[8] Pump seals
[9] Fan belt
ADAP-KOOL
®
Drive Programming Guide 3 Parameter Description
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark
189
3