23-11 Maintenance Action
Option: Function:
Select the action to be associated with the Preventive Maintenance Event.
[1] * Lubricate
[2] Clean
[3] Replace
[4] Inspect/Check
[5] Overhaul
[6] Renew
[7] Check
23-12 Maintenance Time Base
Option: Function:
Select the time base to be associated with the Preventive Maintenance Event.
[0] * Disabled
Disabled
[0] must be used when disabling the Preventive Maintenance Event.
[1] Running Hours
Running Hours
[1] is the number of hours the motor has been running. Running hours are not reset
at power-on. The
Maintenance Time Interval
must be specified in par.23-13
Maintenance Time
Interval
.
[2] Operating Hours
Operating Hours
[2] is the number of hours the frequency converter has been running. Operating
hours are not reset at power-on. The
Maintenance Time Interval
must be specified in par.
23-13
Maintenance Time Interval
.
[3] Date & Time
Date & Time
[3] uses the internal clock. The date and time of the next maintenance occurrence
must be specified in par.23-14
Maintenance Date and Time
.
23-13 Maintenance Time Interval
Range: Function:
1 h* [1 - 2147483647 h] Set the interval associated with the current Preventive Maintenance Event. This parameter is only
used if
Running Hours
[1] or
Operating Hours
[2] is selected in par.23-12
Maintenance Time Base
.
The timer is reset from par.23-15
Reset Maintenance Word
.
Example:
A Preventive Maintenance Event is set up Monday at 8:00. par.23-12
Maintenance Time Base
is
Operating hours
[2] and par.23-13
Maintenance Time Interval
is 7 x 24 hours=168 hours. Next
Maintenance Event will be indicated the following Monday at 8:00. If this Maintenance Event is not
reset until Tuesday at 9:00, the next occurrence will be the following Tuesday at 9:00.