Use par.3-10
Preset Reference
as another example:
Choose the parameter, press [OK], and use the up/down navigation keys keys to scroll through the indexed values. To change the parameter value,
select the indexed value and press [OK]. Change the value by using the up/down keys. Press [OK] to accept the new setting. Press [CANCEL] to abort.
Press [Back] to leave the parameter.
2.1.14 Initialisation to Default Settings
Initialise the frequency converter to default settings in two ways:
Recommended initialisation (via par.14-22
Operation Mode
)
1. Select par.14-22
Operation Mode
2. Press [OK]
3. Select “Initialisation”
4. Press [OK]
5. Cut off the mains supply and wait until the display turns off.
6. Reconnect the mains supply - the frequency converter is now
reset.
7. Change par.14-22
Operation Mode
back to
Normal Operation
.
NB!
Resets parameters selected in Personal Menu with default factory setting.
par.14-22
Operation Mode
initialises all except:
par.14-50
RFI Filter
par. 8-30
Protocol
par.8-31
Address
par.8-32
Baud Rate
par.8-35
Minimum Response Delay
par.8-36
Maximum Response Delay
par.8-37
Maximum Inter-Char Delay
par.15-00
Operating Hours
to par.15-05
Over Volt's
par.15-20
Historic Log: Event
to par.15-22
Historic Log: Time
par.15-30
Alarm Log: Error Code
to par.15-32
Alarm Log: Time
Manual initialisation
1. Disconnect from mains and wait until the display turns off.
2a. Press [Status] - [Main Menu] - [OK] at the same time while power up for LCP 102, Graphical Display
2b. Press [Menu] while power up for LCP 101, Numerical Display
3. Release the keys after 5 s.
4. The frequency converter is now programmed according to default settings.
This procedure initializes all except: par.15-00
Operating Hours
; par.15-03
Power Up's
; par.15-04
Over Temp's
; par.15-05
Over Volt's
.
NB!
When you carry out manual initialisation, you also reset serial communication, par.14-50
RFI Filter
and fault log settings.
Removes parameters selected in par. 25-00
Pack Controller
.
NB!
After initialization and power cycling, the display will not show any information until after a couple of minutes.