AK-LM 330 RS8FR302 © Danfoss 2015-08 55
Check of settings
1.Go to the overview
2. Select thermostats
3. Overview for thermostats
4. Move on with settings for thermostat 1
!
Before the control starts, we check that all the settings are as they should
be.
The overview display will now show one line for each of the general
functions. Behind each icon there is a number of displays with the
dierent settings. It is all these settings that have to be checked.
Remember the settings at the bottom of the pages – the ones that can
only be seen via the ”Scroll bar”.
!
When this function is set to 'YES', a relay will be reserved which couples
with the thermostat. Denition of the connection point must be done
during the I/O conguration.
(In our example, the setting is NO in Thermostats 1 and 2. And YES in
Thermostat 3).
The two DI inputs are used if the thermostat's alarm function is to be
changed temporarily during daily operation:
• Defrosting signal. Signal on the DI input entails change to Delay Time 2.
• Alarm stop. Signal on the DI input stops alarms.
(In our example, both settings have been used in Thermostat 2. Here the
settings are DI1 and DI2 respectively).

Other manuals for Danfoss AK-LM 330

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss AK-LM 330 and is the answer not in the manual?

Danfoss AK-LM 330 Specifications

General IconGeneral
BrandDanfoss
ModelAK-LM 330
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals