EasyManuals Logo

Danfoss BOCK FK40 User Manual

Danfoss BOCK FK40
26 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #15 background imageLoading...
Page #15 background image
D
GB
F
E
PT
I
TR
Ru
© Danfoss | Climate Solutions | 2023.07
AQ453249013813en-000201| 15
5| Commissioning
Make sure that the suction and discharge line valves are open.
Withthecompressorswitchedoff,addtheliquidrefrigerantdirectlytothecondenserorreceiver,
breaking the vacuum.
If the refrigerant needs topping up after starting the compressor, it can be topped up in vapour
formonthesuctionside,or,takingsuitableprecautions,alsoinliquidformattheinlettothe
evaporator.
After starting, check the compressor's oil level.
Drive motor in operating condition "High idle".
Compressor run time min. 10 minutes.
The system should have reached Operating point and steady state
Checkoillevel.Astheinstallationlocationofthecompressorcandifferinpractice(inclinations),it
is recommended that the oil level is checked in both sight glasses. The oil level must be visible in
at least one sight glass.
5.5 Refrigerant charge
5.6 Oil level check
5.7 Shaft seal
CAUTION
Wear personal protective clothing such as goggles and protective
gloves!
ATTENTION Avoidoverllingthesystemwithrefrigerant!
To avoid shifts in concentration, zeotropic refrigerant blends
mustalwaysbeaddedtotherefrigeratingplantinliquidform.
Donotpourliquidrefrigerantthroughthesuctionlinevalveonthe
compressor.
It is not permissible to mix additives with the oil and refrigerant.
ATTENTION After a compressor is replaced, the oil level must be checked again.
If the level is too high, oil must be drained off (risk of oil impact,
reduced performance of the air-conditioning system).
ATTENTION Failure to observe the following instructions can cause loss of
refrigerant and damage to the shaft seal!
INFO The shaft seal seals and lubricates with oil. An oil leakage of
0.05 ml per operating hour is therefore normal. This applies
particularly during the run-in phase (200 - 300 h).
Totrapandcollectleakedoil,theFK40isttedwithaninte-
grated leak oil trapping device with oil reservoir (P.6, Fig. 1).

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss BOCK FK40 and is the answer not in the manual?

Danfoss BOCK FK40 Specifications

General IconGeneral
BrandDanfoss
ModelBOCK FK40
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals