16 | AQ453249013813en-000201
© Danfoss | Climate Solutions | 2023.07
5| Commissioning
The compressor shaft is sealed to outside using a shaft seal. The sealing element rotates with the
shaft.
The following is especially important to ensuring fault-free operation:
The complete refrigerant circuit must be correctly executed and clean inside.
Heavy shocks and vibrations to the shaft as well as continuous cyclic operation are to be avoided.
Thesealingsurfacescansticktogetherduringprolongeddowntimes(e.g.winter).Therefore,run
the system every 4 weeks for 10 minutes.
5.8 Avoidingliquidshocks
Toavoidliquidshocks,thefollowingpointsshouldbeobserved:
The complete refrigeration plant must be correctly designed and executed.
The capacities of all components must be compatible (particularly evaporator and expansion
valve).
Suction gas superheating at the evaporator output should be at least 7 – 10 K (check setting of
theexpansionvalve).
Thesystemmustreachastateofequilibrium.
Particularly incritical systems (e.g. several evaporator points), suitable measures, e.g. use of
liquidtraps,solenoidvalveintheliquidline,etc.arerecommended.
ATTENTION Slugging can damage the compressor and cause refrigerant to
leak.
6.1 Preparation
6.2 Work to be carried out
Oil change: Inprinciple,anoilchangeisnotamandatoryrequirement,iftheequipmentiscorrectly
manufactured and properly operated. Based on decades of experience, we recommend however that
the following oil change/service work is carried out:
• Initialoilchangeduringtherstmaintenanceofthevehicle(atthelatestafteroneyear)
• Thenafterevery5,000operatinghours,atthelatesthoweverafter3years.Alsocleantheoillter.
• An oil change is also necessary, if the oil is very cloudy and dark, or after repairs have been carried
out on the compressor.
Emptying the shaft seal oil reservoir:Asrequireddependingonuse,butatthelatestafter1year
or approx. 1,400 operating hours
WARNING Before starting any work on the compressor:
Switch off the compressor and secure it to prevent a restart.
Relieve compressor of system pressure.
Preventairfrominltratingthesystem!
After maintenance has been performed:
Connect safety switch.
Evacuate compressor.
Release switch lock.
6| Maintenance