4| Compressor assembly
4.1 Setting up
4.2 Maximum permissible inclination
A
max. 30°,
max. 2 minutes
a
max. 15°,
continuous
operation
Fig. 4
Fig. 5
Transportandsuspensionunitontheeyebolt(Fig.4)ordirectonthedischargelinevalve
(Fig.5).
Storage at (-40°C) - (+100°C), maximum permissible relative humidity 10% - 95%, no
condensation.
Fittings (e.g. pipe holders, additional units etc.) on the compressor are permissible only
following consultation with Bock.
Setuponanevensurfaceorframewithsufcientload-bearingcapacity.Useall4fastening
points.
Correct setup of the compressor and mounting of the belt drive are decisive for running comfort,
operating safety and the service life of the compressor.
Fig. 6
INFO Newcompressorsarefactory-lledwithinertgas.Leavethisser-
vice charge in the compressor for as long as possible and prevent
the ingress of air.
Check the compressor for transport damage before starting any
work.
ATTENTION Poor lubrication can damage the compressor. Respect the stated
values.
WARNING Movecompressorsonlywithhoiststhathaveadequateload-bear-
ing capacity.