The valve is maintenance free.
However, constant leakage can occur after blowing off due to abnormal operating conditions. This
leads to reduced performance and increases the compressed gas temperature. In this case check the
valve and replace as necessary.
6.5 Integrated decompression valve
6.4 Recommended spare parts/accessories
6.7 Decommissioning
Close the shut-off valve on the compressor. Drain the refrigerant (it must not be discharged directly
intotheenvironment)anddisposeofitaccordingtotheregulations.Whenthecompressorisdepres-
surised, undo the fastening screws of the shut-off valves. Remove the compressor using an appropri-
ate hoist. Dispose of the oil inside in accordance with the valid national regulations.
6.6 Lubricants / Oils
Theoiltypelledasstandardinthefactoryismarkedonthenameplate,andthisshouldalwaysbe
used,eveninthecaseofmaintenanceunits.Alternativeoiltypescanvarysignicantlyinqualitydue
to additives or inferior raw materials by the manufacturer. Validation within the compressors entire
operating limits can not be guaranteed, if such alternative oil types are used. It is for this reason, that
we only recommend the use of oil from Bock! Bock assumes no liability for any damage arising from
alternative oil types.
Refrigerant Bock standard oil grade
HFC
(e.g.R134a,R407,R404A)
BOCK lub E55
HCFC(e.g.R22) BOCK lub A46
6| Maintenance
Maintenance set for oil change
• BOCK lub E55 2 x 1 l
• Oil drain screw with seal
Maintenance set for shaft seal
• shaft seal kit
• BOCK lub E55 2 x 1 l
• Oil drain screw with seal
Available spare parts and accessories can be found on our compressor selection tool under
vap.bock.de as well as in our online spare parts catalogue at bockshop.bock.de.
Only use original Bock spare parts!