Operating Guide
VLT® AutomationDrive FC 302
90-710 kW, D9h-D10h and E5h-E6h Enclosed Drives
drives.danfoss.com

Table of Contents

Questions and Answers

  • C
    Crystal SmithSep 15, 2025
    What to do for an inrush fault in Danfoss DC Drives?
    • C
      charles18Sep 16, 2025
      If your Danfoss DC Drives are showing an inrush fault, it means too many power-ups have occurred within a short time period. Let the unit cool to operating temperature.
  • E
    ellen22Aug 30, 2025
    What causes line power current imbalance greater than 3% in Danfoss D9h?
    • J
      jonesmckenzieAug 30, 2025
      If you notice a line power current imbalance greater than 3% in your Danfoss DC Drives, it could be a problem with the line power supply itself. Check the line power supply. If the imbalance remains on the same input terminal, there may be a problem with the unit, and you should contact the supplier.
  • H
    Heather TaylorAug 27, 2025
    Why Danfoss DC Drives power on with red light?
    • P
      patricia85Aug 27, 2025
      If your Danfoss DC Drives show 'Power On' and the indicator is red, this typically indicates an IP Address Conflict. Resolve the IP conflict.
  • M
    Marie BrooksSep 23, 2025
    What to do if option configuration has changed in Danfoss DC Drives?
    • W
      Whitney LeeSep 23, 2025
      If the option configuration has changed in Danfoss DC Drives, it means one or more options have either been added or removed since the last power-down. Check that the configuration change is intentional and reset the unit.
  • E
    Emily JacksonSep 18, 2025
    What to do if motor phase V is missing in Danfoss DC Drives?
    • L
      Lisa MelendezSep 18, 2025
      If your Danfoss DC Drives report that motor phase V is missing, remove the power from the frequency converter and check motor phase V.
  • V
    Victoria OliverSep 1, 2025
    What to do if Danfoss D9h show External error DI1?
    • R
      Richard LozanoSep 1, 2025
      If your Danfoss DC drive is showing 'External error DI1', it could be due to a safety input connected to DI1 having an illegal signal level, or the sensor might be broken. You can resolve this by checking that the configuration of DI1 (parameter 42-21 Type, sub-index [0]) is set correctly and that the connected sensor is installed according to specification. Additionally, you can extend the discrepancy time for DI1 using the VLT® Motion Control Tool MCT 10 Safe Plug-in.
  • R
    raymond53Sep 3, 2025
    What to do if Danfoss DC Drives show an earth fault?
    • E
      Edward CarrilloSep 3, 2025
      If your Danfoss DC Drives indicates an earth fault, it means there's current leaking from the output phases to ground, either in the cable between the frequency converter and the motor, or within the motor itself. The solution is to remove power to the frequency converter and repair the earth fault.
  • A
    alexandra88Sep 7, 2025
    What to do for option detection issues in Danfoss D9h DC Drives?
    • J
      Jason DouglasSep 7, 2025
      If your Danfoss DC Drives detects a change in the option layout, enable option layout changes to apply the change.
  • A
    Annette PadillaSep 13, 2025
    How to troubleshoot motor thermistor overtemp in Danfoss DC Drives?
    • C
      Christine DavisSep 13, 2025
      If you are getting a motor thermistor overtemp warning on your Danfoss DC Drives, check whether the thermistor is disconnected. Also, check for motor overheating and if the motor is mechanically overloaded. When using terminal 53 or 54, ensure the thermistor is correctly connected between either terminal 53 or 54 (analog voltage input) and terminal 50 (+10 V supply), and that the terminal switch for 53 or 54 is set for voltage. If using terminal 18, 19, 31, 32, or 33 (digital inputs), ensure the thermistor is correctly connected between the digital input terminal used (digital input PNP only) and terminal 50.
  • A
    Alexander MoraAug 25, 2025
    What to do if Danfoss DC Drives show an over current error?
    • E
      Edwin CamposAug 25, 2025
      If you are experiencing an over current error with your Danfoss DC Drives, it might be due to shock loading or quick acceleration with high-inertia loads. First, remove the power and check if the motor shaft can be turned. Also, verify that the motor size matches the frequency converter and that the motor data is correctly set in parameters 1-20 to 1-25.