Operating Guide
VLT® AutomationDrive FC 302
90-710 kW, D9h-D10h and E5h-E6h Enclosed Drives
drives.danfoss.com

Table of Contents

Questions and Answers

  • M
    Michael MckinneySep 14, 2025
    What does control word timeout mean on Danfoss D9h DC Drives?
    • F
      Frederick MaxwellSep 14, 2025
      If you're experiencing a control word timeout with your Danfoss DC Drives, it means there is no communication to the frequency converter. To resolve this, check the connections on the serial communication cable, increase parameter 8-03 Control Word Timeout Time, check the operation of the communication equipment, and verify that proper EMC installation was performed.
  • R
    Robert DunnSep 10, 2025
    What to do if brake check failed on Danfoss D9h DC Drives?
    • Z
      zdavilaSep 10, 2025
      If the brake check failed on your Danfoss DC Drives, it means the brake resistor is not connected or not working. Check 2-15 Brake Check.
  • K
    Katie JohnsonSep 8, 2025
    What to do if there is no safety option on Danfoss DC Drives?
    • E
      Emily McgrathSep 8, 2025
      If the safety option was removed without applying a general reset on your Danfoss DC Drives, reconnect the safety option.
  • K
    Kenneth WilliamsAug 28, 2025
    How to troubleshoot a motor not reaching maximum speed on Danfoss D9h DC Drives?
    • N
      nicholas26Aug 28, 2025
      If the motor is not reaching its maximum speed using Danfoss DC Drives, program the correct frequency limits. Also, ensure that the reference input signal is scaled correctly by adjusting the settings.
  • E
    Erin ArnoldAug 28, 2025
    Why is the motor speed unstable in my Danfoss DC Drives?
    • J
      Jessica CunninghamAug 28, 2025
      If the motor speed is unstable in your Danfoss DC Drives, check the settings in parameter group 1-6* Load Depen. Setting. For closed loop operation, check settings in parameter group 20-0* Feedback.
  • D
    Debra Murillo MDAug 29, 2025
    What causes a motor to run rough with Danfoss D9h DC Drives?
    • L
      Lisa RayAug 29, 2025
      If the motor runs rough with Danfoss DC Drives, check the motor settings in parameter groups 1-2* Motor Data, 1-3* Adv Motor Data, and 1-5* Load Indep. Setting to avoid over-magnetisation.
  • S
    Steven PorterAug 29, 2025
    Why won't the motor brake with Danfoss DC Drives?
    • W
      William AndersonAug 29, 2025
      If the motor will not brake using Danfoss DC Drives, check parameter group 2-0* DC Brake and 3-0* Reference Limits for possible incorrect settings in the brake parameters or ramp down times that are too short.
  • E
    Emily JacksonSep 18, 2025
    What to do if motor phase V is missing in Danfoss DC Drives?
    • L
      Lisa MelendezSep 18, 2025
      If your Danfoss DC Drives report that motor phase V is missing, remove the power from the frequency converter and check motor phase V.
  • M
    Margaret NelsonSep 23, 2025
    What to do for DC overvoltage on Danfoss DC Drives?
    • E
      Elizabeth Lozano MDSep 23, 2025
      To address DC overvoltage on Danfoss DC Drives, connect a brake resistor and extend the ramp time.
  • S
    Stephanie MillerSep 9, 2025
    What does '1.8 V supply low' mean on Danfoss D9h DC Drives?
    • M
      Michelle ArmstrongSep 9, 2025
      If the 1.8 V DC supply is low on your Danfoss DC Drives, it indicates that the 1.8 V DC supply used on the control card is outside of allowable limits. Check for a defective control card.