5.10.3   Zero point calibration of 
analogue output
Calibration     AO 1
320   0
With this menu item you can adjust the zero point of the analogue output (4mA). The zero point 
correction is only possible when the minimum output is 2 V or 4 mA, i.e. not possible when minimum 
output is 0 V or 0 mA.
The error message of the output monitoring is suppressed as long as the menu Calibration AO is open. 
Therefore, connect the ampere meter (measuring range 20 mA DC) to the analogue output only after 
having opened the menu.
Calibration   AO 1
Connect ampere meter to the analogue output.
Calibration     AO 1
320   323
Adjust the zero offset on the right by changing the offset value 
slowly, until the ampere meter shows the desired value.
Display of the current zero offset on the left.
Calibration     AO 1
SAVE
Save the adjusted zero offset.
Calibration     AO 1
323 323
Return to the display of the current zero offset.
5.11 Addressing
Set Address
          4
Addressing
Assignment of the MODBUS address of the device for system integration, e.g. with 
Danfoss front end type AK-SM 800.
Define the MODBUS address.
Symbol Description Default Function
4 MODBUS Address 0 0 =  Device is not addressed, BUS not used. Max. value is 240.
User Guide | Danfoss Gas sensor, type DGS