1.  Intended use This document has the intent to provide the guidelines to avoid possible damages deriving from 
overvoltage and other possible issues resulting from the connection to the DGS power supply and 
the serial communication network. Moreover it provides the operations executed via handheld 
Service Tool. The display of the hand-held Service Tool and the MODBUS interface for integration with 
Building Management Systems is used as interface for operation, commissioning and calibration of 
the DGS gas detection unit.
2. Introduction
For what concerns display devices, this user guide contains the maximum possible functionality.
Depending on the DGS type some features described here are not applicable and therefore the menu 
items may be hidden.
Some special features are available via the hand-held Service Tool interface only (not via MODBUS). 
This includes the calibration routine and certain properties of the sensor head.
3.  Installation and 
maintenance
This unit must be installed by a suitably qualified 
technician who will install this unit in accordance 
with these instructions and the standards set 
down in their particular industry/country. 
Suitably qualified operators of the unit should be 
aware of the regulations and standards set down 
by their industry/country for the operation of this 
unit. 
These notes are only intended as a guide, and 
the manufacturer bears no responsibility for the 
installation or operation of this unit. 
Failure to install and operate the unit in 
accordance with these instructions and with 
industry guidelines may cause serious injury 
including death, and the manufacturer will not 
be held responsible in this regard.
It is the installer’s responsibility to adequately 
ensure that the equipment is installed correctly 
and set up according to the environment and the 
application in which the products are being used.
3.2  Regular Test 
3.1  Technician use only!
Please observe that DGS works as a safety 
device securing a reaction to a detected high 
gas concentration. If a leakage occurs, the 
DGS will provide alarm functions, but it will 
not solve or take care of the leakage root 
cause itself.
3.3 Location
For all gases heavier than air, Danfoss 
recommends placing the sensor head app. 30 cm 
(12”) above the floor and, if possible, in the air 
flow. All gases measured with these DGS sensors 
are heavier than air: HFC grp 1, HFC grp 2, HFC 
grp 3, CO and propane.
For further details on Test and Location please see 
the Danfoss Application Guide: “Gas detection in 
refrigeration systems”.
To maintain product performance and comply 
with the local requirements, the DGS must be 
tested regularly.
DGSs are provided with a test button that may be 
activated to validate the alarm reactions. 
Additionally, the sensors must be tested by either 
bump test or calibration.
Danfoss recommends the following minimum 
calibration intervals:
DGS-IR: 60 months
DGS-SC: 12 months
DGS-PE: 6 months
With DGS-IR it is recommended to do an annual 
bump test in years without calibration.
Check local regulations on calibration or testing 
requirements. 
For propane: after exposure to a substantial gas 
leak, the sensor should be checked by bump test 
or calibration and replaced if necessary. 
User Guide | Danfoss Gas sensor, type DGS
© Danfoss | Climate Solutions | 2022.01 BC291049702513en-000201 | 3