Service Settings
EY.65.H4.02
52
10.3.1 Hot Water Settings
This section describes the options you can set in menus under the Hot Water menu
item.
Anti-bacteria function When this function is active, the hot-water temperature is raised once in a 24-hour
period to a user-defined temperature and for a user-defined length of time. The con-
troller accomplishes this by temporarily raising the hot-water temperature setpoint.
The following parameters can be set:
Display text Parameter Default value,
range
Description
Duration
Default value:
0.0 hours
Range:
0-23:45 hours
The period during which the water tem-
perature will be maintained at the in-
creased level. If this parameter is set to
0, the anti-bacteria function is disabled
Start time
Default value:
23:00
Range:
0:00-23:45
The time of day at which the temperature
starts to increase
Temperature
Default value:
70 °C
Range:
1-99 °C
The hot-water temperature setpoint will
be increased to this level

Other manuals for Danfoss ECL 2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL 2000 and is the answer not in the manual?

Danfoss ECL 2000 Specifications

General IconGeneral
BrandDanfoss
ModelECL 2000
CategoryTemperature Controller
LanguageEnglish

Related product manuals