4-13  Motor Speed High Limit [RPM]
Range: Function:
Size re-
lated
*
[0 - 60,000 rpm] Enter  the  maximum  limit for motor speed. The Motor Speed
High Limit can be set to correspond to the manufacturer’s max-
imum rated motor speed. The Motor Speed High Limit must
exceed the setting in par. 4-11 
Motor Speed Low Limit [RPM]
.
Only par. 4-11 or 4-12 will be displayed depending on other pa-
rameters set in the Main Menu, and depending on default set-
tings specific to global geographical locations.
NOTE
The output frequency value of the adjustable frequency drive must not exceed a
value higher than 1/10 of the switching frequency.
4-14  Motor Speed High Limit [Hz]
Range: Function:
Size re-
lated
*
[0 - 1000 Hz] Enter the maximum limit for motor speed. The motor speed high
limit can be set to correspond to the manufacturer’s recom-
mended maximum frequency of the motor shaft. The Motor
Speed High Limit must exceed the setting in par. 4-12 
Motor
Speed Low Limit [Hz]
. Only par. 4-11 or 4-12 will be displayed
depending on other parameters set in the Main Menu, and de-
pending on default settings specific to global geographical lo-
cations.
NOTE
Max. output frequency cannot exceed 10% of the inverter switching frequency (par.
14-01).
3-11  Jog Speed [Hz]
Range: Function:
Size re-
lated
*
[0 - 1000 Hz] The jog speed is a fixed output speed at which the adjustable
frequency drive is running when the jog function is activated.
See also par. 3-80.