Par. No. # Parameter description Default value 4 set-up Change during operation Conver-
sion index
Type
4-1* Motor Limits
4-10 Motor Speed Direction [2] Both directions All set-ups FALSE - Uint8
4-11 Motor Speed Low Limit [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
4-12 Motor Speed Low Limit [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
4-13 Motor Speed High Limit [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
4-14 Motor Speed High Limit [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
4-16 Torque Limit Motor Mode 110.0 % All set-ups TRUE -1 Uint16
4-17 Torque Limit Generator Mode 100.0 % All set-ups TRUE -1 Uint16
4-18 Current Limit ExpressionLimit All set-ups TRUE -1 Uint32
4-19
Max. Output Frequency ExpressionLimit All set-ups FALSE -1 Uint16
4-5* Adj. Warnings
4-50 Warning Current Low 0.00 A All set-ups TRUE -2 Uint32
4-51 Warning Current High ImaxVLT (P1637) All set-ups TRUE -2 Uint32
4-52 Warning Speed Low 0 RPM All set-ups TRUE 67 Uint16
4-53 Warning Speed High outputSpeedHighLimit (P413) All set-ups TRUE 67 Uint16
4-54 Warning Reference Low -999999.999 N/A All set-ups TRUE -3 Int32
4-55 Warning Reference High 999999.999 N/A All set-ups TRUE -3 Int32
4-56 Warning Feedback Low -999999.999 ReferenceFeedbackUnit All set-ups TRUE -3 Int32
4-57 Warning Feedback High 999999.999 ReferenceFeedbackUnit All set-ups TRUE -3 Int32
4-58
Missing Motor Phase Function [1] On All set-ups TRUE - Uint8
4-6* Speed Bypass
4-60 Bypass Speed From [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
4-61 Bypass Speed From [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
4-62 Bypass Speed To [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
4-63 Bypass Speed To [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
4-64 Semi-Auto Bypass Set-up [0] Off All set-ups FALSE - Uint8
4.4.6. 4-** Limits / Warnings
4. How to Program
VLT
®
HVAC DRIVE High Power
Instruction Manual