Par. No. # Parameter description Default value 4 set-up Change during operation Conver-
sion index
Type
8-0* General Settings
8-01 Control Site null All set-ups TRUE - Uint8
8-02 Control Source null All set-ups TRUE - Uint8
8-03 Control Timeout Time ExpressionLimit 1 set-up TRUE -1 Uint32
8-04 Control Timeout Function [0] Off 1 set-up TRUE - Uint8
8-05 End-of-Timeout Function [1] Resume set-up 1 set-up TRUE - Uint8
8-06 Reset Control Timeout [0] Do not reset All set-ups TRUE - Uint8
8-07
Diagnosis Trigger [0] Disable 2 set-ups TRUE - Uint8
8-1* Control Settings
8-10 Control Profile [0] FC profile All set-ups TRUE - Uint8
8-13 Configurable Status Word STW [1] Profile Default All set-ups TRUE - Uint8
8-3* FC Port Settings
8-30 Protocol [0] FC 1 set-up TRUE - Uint8
8-31 Address ExpressionLimit 1 set-up TRUE 0 Uint8
8-32 Baud Rate null 1 set-up TRUE - Uint8
8-33 Parity / Stop Bits null 1 set-up TRUE - Uint8
8-35 Minimum Response Delay ExpressionLimit 1 set-up TRUE -3 Uint16
8-36 Maximum Response Delay ExpressionLimit 1 set-up TRUE -3 Uint16
8-37 Maximum Inter-Char Delay ExpressionLimit 1 set-up TRUE -5 Uint16
8-4* FC MC protocol set
8-40 Telegram Selection [1] Standard telegram 1 2 set-ups TRUE - Uint8
8-5* Digital/Bus
8-50 Coasting Select [3] Logic OR All set-ups TRUE - Uint8
8-52 DC Brake Select [3] Logic OR All set-ups TRUE - Uint8
8-53 Start Select [3] Logic OR All set-ups TRUE - Uint8
8-54 Reversing Select null All set-ups TRUE - Uint8
8-55 Set-up Select [3] Logic OR All set-ups TRUE - Uint8
8-56
Preset Reference Select [3] Logic OR All set-ups TRUE - Uint8
8-7* BACnet
8-70 BACnet Device Instance 1 N/A 1 set-up TRUE 0 Uint32
8-72 MS/TP Max Masters 127 N/A 1 set-up TRUE 0 Uint8
8-73 MS/TP Max Info Frames 1 N/A 1 set-up TRUE 0 Uint16
8-74 "I-Am" Service [0] Send at power-up 1 set-up TRUE - Uint8
8-75
Initialization Password ExpressionLimit 1 set-up TRUE 0 VisStr[20]
8-8* FC Port Diagnostics
8-80 Bus Message Count 0 N/A All set-ups TRUE 0 Uint32
8-81 Bus Error Count 0 N/A All set-ups TRUE 0 Uint32
8-82 Slave Message Count 0 N/A All set-ups TRUE 0 Uint32
8-83 Slave Error Count 0 N/A All set-ups TRUE 0 Uint32
4.4.9. 8-** Communication and Options
VLT
®
HVAC DRIVE High Power
Instruction Manual
4. How to Program
MG.11.F1.22 - VLT
®
is a registered Danfoss trademark.
95