Parameter Option Default Usage
6-10 Terminal 53 Low Voltage
0–10 V 0.07 V Enter the voltage that corresponds to the low
reference value.
6-11 Terminal 53 High Voltage
0–10 V 10 V Enter the voltage that corresponds to the
high reference value.
6-12 Terminal 53 Low Current 0–20 mA 4 Enter the current that corresponds to the low
reference value.
6-13 Terminal 53 High Current
0–20 mA 20 Enter the current that corresponds to the high
reference value.
6-19 Terminal 53 mode
[0] Current
[1] Voltage
1 Select if terminal 53 is used for current- or
voltage input.
30-22 Locked Rotor Detection
[0] Off
[1] On
[0] Off
30-23 Locked Rotor Detection Time [s]
0.05–1 s 0.10 s
Table 4.4 Set-up Wizard for Open Loop Applications
Programming Quick Guide