EasyManuals Logo

Danfoss FC 101 User Manual

Danfoss FC 101
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #8 background imageLoading...
Page #8 background image
3 Installation
3.1 Mechanical Installation
3.1.1 Side-by-Side Installation
The frequency converter can be mounted side-by-side but requires the clearance above and below for cooling.
Power [kW(HP)]
Clearance above/below [mm(in)]
Frame IP class 3x200-240 V 3x380-480 V 3x525-600 V
H1 IP20 0.25-1.5 (0.33-2) 0.37-1.5 (0.5-2) 100 (4)
H2 IP20 2.2 (3) 2.2-4 (3-5) 100 (4)
H3 IP20 3.7 (5) 5.5-7.5 (7.5-10) 100 (4)
H4 IP20 5.5-7.5 (7.5-10) 11-15 (15-20) 100 (4)
H5 IP20 11 (15) 18.5-22 (25-30) 100 (4)
H6 IP20 15-18.5 (20-25) 30-45 (40-60) 18.5-30 (25-40) 200 (7.9)
H7 IP20 22-30 (30-40) 55-75 (70-100) 37-55 (50-70) 200 (7.9)
H8 IP20 37-45 (50-60) 90 (125) 75-90 (100-125) 225 (8.9)
H9 IP20 2.2-7.5 (3-10) 100 (4)
H10 IP20 11-15 (15-20) 200 (7.9)
I2 IP54 0.75-4.0 (1-5) 100 (4)
I3 IP54 5.5-7.5 (7.5-10) 100 (4)
I4 IP54 11-18.5 (15-25) 100 (4)
I6 IP54 22-37 (30-50) 200 (7.9)
I7 IP54 45-55 (60-70) 200 (7.9)
I8 IP54 75-90 (100-125) 225 (8.9)
Table 3.1 Clearance Required for Cooling
NOTICE
With IP21/NEMA Type1 option kit mounted, a distance of 50 mm (2 in) between the units is required.
Installation Quick Guide
6 Danfoss A/S © 08/2014 All rights reserved. MG18A602
33

Other manuals for Danfoss FC 101

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 101 and is the answer not in the manual?

Danfoss FC 101 Specifications

General IconGeneral
ModelFC 101
ManufacturerDanfoss
Protection ClassIP20
Relative Humidity95% (non-condensing)
Communication InterfaceRS-485

Related product manuals