8.8.2 UL Compliance
1 x 200-240 V
Recommended max. fuse
Power
[kW]
Max
prefuse
size [A]
Buss-
mann
JFHR2
Buss-
mann
RK1
Buss-
mann
J
Buss-
mann
T
Buss-
mann
CC
Buss-
mann
CC
Buss-
mann
CC
SIBA
RK1
Littel
fuse
RK1
Ferraz-
Shawmut
CC
Ferraz-
Shawmut
RK1
Ferraz-
Shawmut
J
1.1 15 FWX-15
KTN-
R15
JKS-
15
JJN-
15
FNQ-
R-15
KTK-
R-15
LP-
CC-15
5017906-
016
KLN-
R15 ATM-R15 A2K-15R HSJ15
1.5 20 FWX-20
KTN-
R20
JKS-
20
JJN-
20
FNQ-
R-20
KTK-
R-20
LP-
CC-20
5017906-
020
KLN-
R20 ATM-R20 A2K-20R HSJ20
2.2 30* FWX-30
KTN-
R30
JKS-
30
JJN-
30
FNQ-
R-30
KTK-
R-30
LP-
CC-30
5012406-
032
KLN-
R30 ATM-R30 A2K-30R HSJ30
3.0 35 FWX-35
KTN-
R35
JKS-
35
JJN-
35 ---
KLN-
R35 --- A2K-35R HSJ35
3.7 50 FWX-50
KTN-
R50
JKS-
50
JJN-
50
5014006-
050
KLN-
R50 --- A2K-50R HSJ50
5.5 60** FWX-60
KTN-
R60
JKS-
60
JJN-
60
5014006-
063
KLN-
R60 --- A2K-60R HSJ60
7.5 80 FWX-80
KTN-
R80
JKS-
80
JJN-
80
5014006-
080
KLN-
R80 --- A2K-80R HSJ80
15 150 FWX-150
KTN-
R150
JKS-
150
JJN-
150
2028220-
150
KLN-
R150 A2K-150R HSJ150
22 200 FWX-200
KTN-
R200
JKS-
200
JJN-
200
2028220-
200
KLN-
R200 A2K-200R HSJ200
Table 8.11 1 x 200-240 V
* Siba allowed up to 32 A ; ** Siba allowed up to 63 A
3x200-240 V
Recommended max. fuse
Power
[kW]
Bussmann
Type RK1
1)
Bussmann
Type J
Bussmann
Type T
Bussmann
Type CC
Bussmann
Type CC
Bussmann
Type CC
1.1 KTN-R-10 JKS-10 JJN-10 FNQ-R-10 KTK-R-10 LP-CC-10
1.5 KTN-R-15 JKS-15 JJN-15 FNQ-R-15 KTK-R-15 LP-CC-15
2.2 KTN-R-20 JKS-20 JJN-20 FNQ-R-20 KTK-R-20 LP-CC-20
3.0 KTN-R-25 JKS-25 JJN-25 FNQ-R-25 KTK-R-25 LP-CC-25
3.7 KTN-R-30 JKS-30 JJN-30 FNQ-R-30 KTK-R-30 LP-CC-30
5.5/7.5 KTN-R-50 KS-50 JJN-50 - - -
11 KTN-R-60 JKS-60 JJN-60 - - -
15 KTN-R-80 JKS-80 JJN-80 - - -
18.5-22 KTN-R-125 JKS-125 JJN-125 - - -
30 KTN-R-150 JKS-150 JJN-150 - - -
37 KTN-R-200 JKS-200 JJN-200 - - -
45 KTN-R-250 JKS-250 JJN-250 - - -
Table 8.12 3x200-240 V, Enclosure Types A, B and C
Specifications Instruction Manual
64 Danfoss A/S © Rev. 2014-04-10 All rights reserved. MG16E322