FCM 300 Series
MG.03.B6.2G - VLT is a registered Danfoss trademark
✭ = General factory setting - also applying to spare part unit,
HH
HH
H = HVAC setting,
II
II
I = Industrial setting,
( ) = display text [ ] = value for use in communication via serial communication port
Parameter Group 0: Operation & Display
DC link voltage [V] (DC LINK VOLTAGE [V]) [12]
Thermal load, FC [%] (FC THERMAL [%]) [14]
Hours run [Hours] (RUNNING HOURS) [15]
Digital input [Binary code] (DIGITAL INPUT [BIN]) [16]
External reference [%] (EXTERNAL REF [%]) [21]
Status word [Hex] (STATUS WORD [HEX]) [22]
Heat sink temp. [°C] (HEATSINK TEMP [°C]) [25]
Alarm word [Hex] (ALARM WORD [HEX]) [26]
Control word [Hex] (CONTROL WORD [HEX]) [27]
Warning word 1 [Hex]
(WARNING WORD 1 [HEX]) [28]
Warning word 2 [Hex]
(WARNING WORD 2 [HEX]) [29]
Analog input 1 [mA] (ANALOG INPUT 1 [mA]) [30]
Analog input 2 [V] (ANALOG INPUT 2 [V]) [31]
Function:
This parameter allows a choice of the data value to
be displayed in line 2 of the display.
Parameters 010-012 enable the use of three
additional data values to be displayed in line 1.
NOTE!
In parameter 009, "none" [0] cannot be selected.
Description of choice:
ReferenceReference
ReferenceReference
Reference
[%] [%]
[%] [%]
[%] corresponds to the total reference
(sum of digital/analog/preset/bus/freeze ref./catch-
up and slow-down).
Reference Reference
Reference Reference
Reference
[unit][unit]
[unit][unit]
[unit] gives the sum of the references
using the unit stated on the basis of configuration in
parameter 100 (Hz, Hz and rpm).
FeedbackFeedback
FeedbackFeedback
Feedback
[unit] [unit]
[unit] [unit]
[unit] gives the status value of terminal 1
and 2 using the unit/scale selected in parameter
414, 415 and 416.
FrequencyFrequency
FrequencyFrequency
Frequency
[Hz] [Hz]
[Hz] [Hz]
[Hz] gives the motor frequency, i.e. the
output frequency to the motor.
Frequency x ScalingFrequency x Scaling
Frequency x ScalingFrequency x Scaling
Frequency x Scaling
[-] [-]
[-] [-]
[-] corresponds to the present
motor frequency f
M
multiplied by a factor (scaling) set
in parameter 008.
Motor currentMotor current
Motor currentMotor current
Motor current
[A] [A]
[A] [A]
[A] states the phase current of the
motor measured as effective value.
TT
TT
T
orqueorque
orqueorque
orque
[%] [%]
[%] [%]
[%] gives the current motor load in relation
to the rated motor torque.
PowerPower
PowerPower
Power
[kW] [kW]
[kW] [kW]
[kW] states the actual power consumed by
the motor in kW.
PowerPower
PowerPower
Power
[HP] [HP]
[HP] [HP]
[HP] states the actual power consumed by
the motor in HP.
Motor voltageMotor voltage
Motor voltageMotor voltage
Motor voltage
[V] [V]
[V] [V]
[V] states the voltage supplied to the
motor.
DC link voltageDC link voltage
DC link voltageDC link voltage
DC link voltage
[V] [V]
[V] [V]
[V] states the intermediate circuit
voltage in the FCM 300.
Thermal load, FC Thermal load, FC
Thermal load, FC Thermal load, FC
Thermal load, FC
[%] [%]
[%] [%]
[%] states the calculated/
estimated thermal load on the FCM 300. 100% is
the cut-out limit.
Hours runHours run
Hours runHours run
Hours run
[Hours] [Hours]
[Hours] [Hours]
[Hours] states the number of hours that
the motor has run since the latest reset in
parameter 619.
Digital inputDigital input
Digital inputDigital input
Digital input
[Binary code] [Binary code]
[Binary code] [Binary code]
[Binary code] states the signal states
from the 4 digital terminals (2, 3, 4 and 5). Input 5
corresponds to the bit at the far left. '0' = no signal,
'1' = connected signal.
External referenceExternal reference
External referenceExternal reference
External reference
[%] [%]
[%] [%]
[%] gives the sum of the external
reference as a percentage (the sum of analog/pulse/
bus).
Status wordStatus word
Status wordStatus word
Status word
[Hex] [Hex]
[Hex] [Hex]
[Hex] gives the status word sent via
the serial communication port in Hex code from the
FCM 300.
Heat sinkHeat sink
Heat sinkHeat sink
Heat sink
temp. temp.
temp. temp.
temp.
[°C] [°C]
[°C] [°C]
[°C] states the present heat sink
temperature of the FCM 300. The cut-out limit is 90 ±
5°C; cutting back in occurs at 60 ± 5°C.
Alarm word Alarm word
Alarm word Alarm word
Alarm word
[Hex][Hex]
[Hex][Hex]
[Hex] indicates one or several alarms in
a Hex code.
Control word. Control word.
Control word. Control word.
Control word.
[Hex] [Hex]
[Hex] [Hex]
[Hex] indicates the control word for
the FC motor. See Serial communication.
Warning word 1.Warning word 1.
Warning word 1.Warning word 1.
Warning word 1.
[Hex] [Hex]
[Hex] [Hex]
[Hex] indicates one or more
warnings in a Hex code.
Warning word 2.Warning word 2.
Warning word 2.Warning word 2.
Warning word 2.
[Hex] [Hex]
[Hex] [Hex]
[Hex] indicates one or more
status states in a Hex code.
Analog input 1 [mA]Analog input 1 [mA]
Analog input 1 [mA]Analog input 1 [mA]
Analog input 1 [mA], states the signal value on
terminal 1.
Analog input 2 [V]Analog input 2 [V]
Analog input 2 [V]Analog input 2 [V]
Analog input 2 [V], states the signal value on
terminal 2.
010 Display line 1.1 (DISPLAY LINE 1.1)
Value:
✭ Reference [%] [1]
See parameter 009.
Function:
This parameter enables a choice of the first of three
data values to be shown on the display, line 1,
position 1.
For display read-outs, press the [DISPLAY/STATUS]
button.
8-5