Adjustment spindles location
Note
Remove lockplate before thermostat
adjustment. Replace lockplate after
adjustment (if desired).
RANGE DIFFERENTIAL
See printed instruction on top of control  See printed instruction on top of control
  increase temp. (warmer): turn CW    Increase: turn CW
  decrease temp. (colder): turn CCW    decrease: turn CCW
(use adjustment knob)  (use adjustment knob or screwdriver)
Determination of dierential
For KP w/ vapor charge and auto. reset (KP 61, KP 62, KP 63, KP 68, KP 69): Use graphs to determine correct dierential.
Example:
HSP = 5.6 °C (45 °F) =>  DIFF (from graph):
LSP = 0 °C (32 °F)     7.2 °C (13 °F) (value which has to be
    set on di. scale).
For KP w/ adsorption charge (KP 71, KP 73, KP 75, KP 77, KP 79, KP 81):
The dierential will be HSP less LSP
Example:  HSP  –   LSP  =  DIFF.
  7 °C   –   5 °C  =  2 °C 
  (45 °F)(35 °F) (10 °F)
Note:
(Load Option A)     (Load Option B)
CUT-IN  =   HSP  or  CUT-IN  =   LSP
CUT-OUT =   LSP    CUT-OUT  =   HSP
See “Wiring”