EasyManuals Logo
Home>Danfoss>Media Converter>MCA 121

Danfoss MCA 121 User Manual

Danfoss MCA 121
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
7 Troubleshooting
7.1.1 Step-by-step Troubleshooting
Check: LEDs
The option contains two LEDs to indicate the state of the device and the network. During normal operation the MS and at
least one NS LED will show a constant green light.
State LED Description
Standby Green: Flashing green The device needs commissioning
Device operational Green: Solid green The device is operational
Major recoverable fault Flashing red The device has detected a recoverable fault (MAR)
Major unrecoverable
fault
Red: Solid red The device has detected a un-recoverable fault
(MAU)
Self test
Red:
Flashing red/
green
The EIP option is in self-test mode
Green:
Table 7.1 MS: Module Status
State LED Description
No connections Green: Flashing green There are no established any CIP connections to
the device
Connected Green: Solid green There is established (at least) one CIP connection to
the device
Connection time-out Red: Flashing red One or more CIP connections has timed-out
Duplicate IP Red: Solid red The IP-address assigned to the device is already in
use
Self test
Red: Flashing red/
green
The EIP option is in self-test mode
Green
Table 7.2 NS1 + NS2: Network Status (one per port)
Check: Link Status
The status of the Ethernet link cannot be directly identified by means of the LEDs, if no CIP connection is established.
Use 12-10 Link Status to verify presents of the link.
Use 12-11 Link Duration to verify that the link is steady present.
The parameter will show the duration of the present link, and preset to 00:00:00:00 if the link is broken.
Check: Cabling
In rare cases of cabling mis-configuration, the option might show the presents of a link, but no communication is running.
Exchange the cable in doubt.
Check: IP Address
Verify that the option has a valid IP address (please refer to section: IP Settings) in 12-01 IP Address. If the option has
identified a duplicate IP Address NS LEDs will light steady red. If the option is set up for BOOTP or DHCP, verify that a
BOOTP or DHCP server is connected in 12-04 DHCP Server. If no server is connected, the parameter will show:
000.000.000.000.
7.1.2 Alarm Word and Warning Word
Alarm word and warning word are shown in the display in Hex format. If there is more than one warning or alarm, a sum of
all warnings or alarms will be shown. Warning word and alarm word are displayed in 16-90 Alarm Word to 16-95 Ext. Status
Word 2. For more information on the individual alarms and warnings, please refer to the frequency converter Design Guide.
Troubleshooting MCA 121 EtherNet/IP
38 MG.90.J3.02 - VLT
®
is a registered Danfoss trademark
77

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss MCA 121 and is the answer not in the manual?

Danfoss MCA 121 Specifications

General IconGeneral
BrandDanfoss
ModelMCA 121
CategoryMedia Converter
LanguageEnglish

Related product manuals