Fault monitoring overview
Type Fault
monitoring
Delay before error
out
Error mode Error output
status
Fault output
on PVE
LED light Memory
†
PVEO
PVEM
No fault monitoring
PVEA
PVEH
PVEP
PVES
PVEU
Active 500 ms
(PVEA: 750 ms)
No fault Low < 2 V Green –
Input signal faults High ~U
DC
Flashing red Yes
Transducer (LVDT) Constant red
Close loop fault
Passive 250 ms
(PVEA: 750 ms)
No fault Low < 2 V Green –
Input signal faults High ~U
DC
Flashing red No
Transducer (LVDT) Constant red
Close loop fault
PVE
Float
six pin
Active 500 ms Float not active High ~U
DC
Constant red Yes
750 ms Float still active
Measured between fault output pin and ground.
†
Reset needed
PVEO
The PVEO is an on/off activated actuator. The PVEO has not fault-monitoring.
Variants:
•
PVEO-R with a ramp delayed actuation
•
PVEO-DI with direction indication feedback
•
Anodized aluminum block
•
ATEX certified
Power supply:
•
12 V
•
24 V
Connectors:
•
AMP
•
DIN/Hirshmann
•
Deutsch
®
AMP version DIN/Hirschmann version Deutsch
®
version
PVEO/PVEO-R
157-502.11
DC
DC
U
U
3
1
2
PVEM
The PVEM is a proportional activated actuator. The PVEM has not fault-monitoring.
Variants:
•
PVEM -R with a ramp delayed actuation
•
PVEM for float in B-direction and max. flow B at 4.8 mm
Power supply: 12 / 24 V
Connectors:DIN/Hirshmann
Technical Information
PVG 32 Proportional Valve Group
Electrical actuation
32 |
©