30
FRCC.PC.007.B8.02
Application guidelines
System design recommendations
A LLSV may be used to isolate the liquid charge 
on the condenser side, thereby preventing 
against charge transfer or excessive migration to 
the compressor during o -cycles. The quantity of 
refrigerant on the low-pressure side of the system 
can be further reduced by using a pump-down 
cycle in association with the LLSV.
Liquid line solenoid valve 
(LLSV)
Pump-down cycle A pump-down cycle represents one of the most 
e ective ways to protect against the o -cycle 
migration of liquid refrigerant. Once the system 
has reached its set point and is about to shut 
o , the LLSV on the condenser outlet closes. 
The compressor then pumps the majority of 
the refrigerant charge into the condenser and 
receiver before the system stops on the low 
pressure pump-down switch. This step reduces 
the amount of charge on the low side in order to 
prevent o -cycle migration. The recommended 
low-pressure pump-down switch setting is 1.5 
bar below the nominal evaporating pressure. 
It shall not be set lower than 2.3 bar(g). For 
suggested wiring diagrams, please see section 
"Suggested wiring diagrams logic".
In certain conditions, the discharge valve in the 
SH090 - 105 - 120 - 140 - 161 - 184 compressor 
may not completely seal and result in compressor 
restarts during pump down applications. An 
external, non-bleeding check valve may need to 
be installed.
Tests for pump down cycle approval:
•  As the pump-down switch setting is inside the 
application envelope, tests should be carried 
out to check unexpected cut-out during 
transient conditions (ie. defrost – cold starting). 
When unwanted cut-outs occur, the low 
pressure pump-down switch can be delayed. In 
this case a low pressure safety switch without 
any delay timer is mandatory.
Sump heater The surface sump heaters are designed to protect 
the compressor against o -cycle migration of 
refrigerant.
When the compressor is idle, the oil temperature 
in the sump of the compressor must be 
maintained at no lower than 10 K above the 
saturation temperature of the refrigerant on the 
low-pressure side. This requirement ensures that 
the liquid refrigerant is not accumulating in the 
sump. A sump heater is only e ective if capable 
of sustaining this level of temperature di erence. 
Tests must be conducted to ensure that the 
appropriate oil temperature is maintained under 
all ambient conditions (temperature and wind). 
Note that below –5°C ambient temperature and a 
wind speed of above 5m/second, we recommend 
that the heaters be thermally insulated in order 
to limit the surrounding energy losses.
Since the total system charge may be unde ned, 
a sump heater is recommended on all stand-
alone compressors and split systems. In addition, 
any system containing a refrigerant charge in 
excess of the maximum recommended system 
charge for compressors requires a sump heater. 
A sump heater is also required on all reversible 
cycle applications. 
At initial start-up or after power shortage, it is 
recommended to energize surface sump heater 
to remove refrigerant 6 hours in advance. A 
quicker start-up is possible by "jogging" the 
compressor to evacuate refrigerant in the 
compressor. Start the compressor for 2 or 3 
seconds, then wait for 1 to 2 minutes. After 3 or 4 
jogs the compressor can be started.
The heater must be energized whenever the 
compressor is o  to avoid liquid refrigerant 
entering the compressor.
Provide separate electrical supply for the heaters 
so that they remain energized even when 
the machine is out of service (eg. Seasonal 
shutdown).
Surface sump heater accessories are available 
from Danfoss (see section "Accessories").