514 Bus time interval function
(BUS TIMEOUT FUNC)
Value:
Off (off) [0]
Freeze output frequency (FREEZE OUTPUT) [1]
Stop (STOP) [2]
Jogging (JOGGING) [3]
Max. speed (MAX SPEED) [4]
Stop and trip (STOP AND TRIP) [5]
Function:
In this parameter you can select the required reaction
for the frequency converter when the preset time in
parameter 513 Bus time interval has been exceeded.
If choices [1] to [5] are activated the output relay will
be deactivated.
Description of choice:
The output frequency of the frequency converter can
be frozen at the present value, stop the motor, be fro-
zen at parameter 213 Jogging frequency, be frozen at
parameter 202 Output frequency, high limit f
MAX
or stop
and activate a cut out.
515-544 Data readout
Value:
Par.
no.
Description Display text Unit Update
interval
515 Res. reference (REFERENCE %) %
516 Res. reference [Unit] (REFERENCE [UNIT]) Hz, rpm
517 Feedback [Unit] (FEEDBACK [UNIT]) Par. 416
518 Frequency (FREQUENCY) Hz
519 Frequency x scale (FREQUENCY X SCALE) Hz
520 Motor current (MOTOR CURRENT) Amp
521 Torque (TORQUE) %
522 Power[kW] (POWER (KW)) kW
523 Power[HP] (POWER (HP)) HP
524 Motor voltage (MOTOR VOLTAGE) V
525 DC-link voltage (DC LINK VOLTAGE) V
526 Thermal load motor (MOTOR THERMAL) %
527 Thermal load inverter (INV. THERMAL) %
528 Digital input (DIGITAL INPUT) Bin
529 Term.53, analogue input (ANALOG INPUT 53) V
531 Term.60, analogue input (ANALOG INPUT 60) mA
532 Pulse reference (PULSE REFERENCE) Hz
533 External ref. (EXT. REF.%) %
534 Status word, Hex (STATUS WORD) Hex
535 Bus feedback 1 (BUS FEEDBACK1) Hex
537 Inverter temperature (INVERTER TEMP.) °C
538 Alarm word (ALARM WORD) Hex
539 Control word (CONTROL WORD) Hex
540 Warning word (WARN. WORD) Hex
541 Extended status word (STATUS WORD) Hex
544 Pulse count (PULSE COUNT)
Function:
These parameters can be read out via the serial com-
munication port and the LCP display. See also param-
eters 009-012 Display readout.
NB!
Parameters 515-541 can only be read out
via an LCP control unit.
= factory setting, () = display text, [] = value for use in communication via serial communication port
126 MG.27.E2.02 - VLT is a registered Danfoss trademark