EasyManua.ls Logo

Danfoss VLT 2800 - Page 58

Danfoss VLT 2800
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
101 = Variable torque medium [3]
If used with centrifugal pumps and fans.
308 = Feedback [2] (for 0-10 V DC transmit-
ters)
or
314 = Feedback [2] (for 4-20 mA transmitters)
414 = Minimum feedback scaling, must be
set to the minimum feedback value
415 = Maximum feedback scaling, must be
set to the maximum feedback value
Example: Pressure transmitter 0-10 bar: 414
= 0 and 415 = 10
416 = Process units: As shown on the local
control panel (example: bar [4])
437 = Normal [0]: The output frequency
should be reduced when the feedback signal
increases
Inverse [1]: The output frequency should in-
crease when the feedback signal increases
440 = Proportional gain (P-gain) 0.3-1.0 (ex-
perienced value)
441 = Integration time (I-time) 3-10 sec. (ex-
perienced value)
442 = Differentiation time (D-time) 0-10 sec.
(experienced value)
205 = Max. reference is to be set equal to
parameter 415 (example: 10 bar)
215 = Preset reference 1. Set the preset ref-
erence to the wanted min. reference value
(example: 5 bar)
(Parameter 205 and 215 are shown in the
process unit chosen in parameter 416).
The value in brackets [ ] are data values cor-
responding to the wanted function. Example:
Parameter 308 Feedback signal = [2]
If the motor is supposed to always run at a
minimum speed, a such can be selected in
parameter 204 = output frequency low limit.
(For pump works it is typically 15-20 Hz).
With the above connections and settings all
normal pump and fan applications will work
properly. In certain cases it might be neces-
sary to optimize the PID-controllerr (parame-
ter 440, 441 and 442) beyond the mentioned
experienced values.
58 MG.27.E2.02 - VLT is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT 2800

Related product manuals