EasyManuals Logo
Home>Danfoss>DC Drives>VLT 3500 Series

Danfoss VLT 3500 Series User Manual

Danfoss VLT 3500 Series
123 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #93 background imageLoading...
Page #93 background image
VLT
®
Series 3500
91
Bit 15,
TIMERS OK/OVERSHOOT:
Bit 15 = “0” means that the timers for thermal motor protec-
tion and thermal drive protection have not exceeded 100%.
Bit 15 = “1” means that one of the timers has exceeded
100%.
Address
Control/status word
Data value
Check-sum
Check-sum: bytes 2-19 = 1007, reduced to 07.
Parameter no.
Example:
The status word below says that the motor is running on
the desired speed reference, but outside the defined fre-
quency area. Consequently, bit 10 = “0” (out of frequency
range) and bit 07 = “1” (warning). Voltage, current and tim-
ers are OK.
Message Example:
A drive, with address 1, is to be given a start signal and a
speed reference that corresponds to 40 Hz.
A start signal is given by means of the control word and the
speed reference is given to parameter 516, bus reference,
80% corresponding to 40 Hz, since the maximum frequency
is 50 Hz. This results in the following message:
Message from the master (PC or PLC) to the frequency converter
Function Byte Number ASCII Character Decimal Value
Start-byte 1 < 60
2048
3149
Control character 4 U 85
5O79
6G71
7D68
8@64
9048
10 5 53
11 1 49
12 6 54
Sign 13 + 43
14 0 48
15 0 48
16 0 48
17 8 56
18 0 48
Decimal point 19 0 48
20 0 48
21 7 55
Stop-byte 22 > 62
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0/10000101110000111
ASCII @ K H G

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 3500 Series and is the answer not in the manual?

Danfoss VLT 3500 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 3500 Series
CategoryDC Drives
LanguageEnglish

Related product manuals