6-20
VLT is a registered Danfoss trademark
Figure 6-13. Fan Assembly (2 of 2)
Inline molex connector (Step 6)
Retaining nut (Step 7)
5. Disconnect in-line molex connector.
6. Remove fan assy by removing 6 (8mm) retaining
nuts from stud. Note that fan assy weighs approx.
18 lbs (8 kg).
Reinstall in reverse order of this procedure. Tighten mounting
nuts to 20 in-lbs (2.25 Nm).