A pre-fuse of min. 6 Amp, slow-blow, can be fitted to protect the external 24 V DC supply. The
power consumption is 15-50 W, depending on the load on the control card.
Use 24 V DC supply of type PELV to ensure correct galvanic isolation (type PELV) on
the control terminals of the frequency converter.
Relay output
Torque: 0.5 - 0.6 Nm (5 in-lbs)
Screw size: M3
No.
Function
1-3 Relay output, 1+3 break, 1+2
make. See the Operating In-
structions.
4, 5 Relay output, 4+5 make. See
the Operating Instructions.
3. Installation
VLT
®
5000/6000/8000
High Power Installation Guide
24