5.1.3 Mechanical Mounting 
1. Drill holes in accordance with the measurements given.
2. You must provide screws suitable for the surface on which you want to mount the frequency converter. Retighten all four screws.
The frequency converter allows side-by-side installation.
The back wall must always be solid.
Enclosure
Air space (mm)
A2
A3
A5
100  
B1
B2
200  
B3 200  
B4 200  
C1 200  
C2 225  
C3 200  
C4 225  
D1/D2/D3/D4 225  
E1/E2 225  
F1/F2/F3/F4 225  
Table 5.1: Required free air space above and below frequency converter
 
5.1.4 Safety Requirements of Mechanical Installation
Pay attention to the requirements that apply to integration and field mounting kit. Observe the information in the list to avoid serious
damage or injury, especially when installing large units.
The frequency converter is cooled by means of air circulation.
To protect the unit from overheating, it must be ensured that the ambient temperature 
does not exceed the maximum temperature stated for the
frequency converter
 and that the 24-hour average temperature 
is not exceeded
. Locate the maximum temperature and 24-hour average in the paragraph
Derating for Ambient Temperature
.
If the ambient temperature is in the range of 45 °C - 55 ° C, derating of the frequency converter will become relevant, see 
Derating for Ambient
Temperature
.
The service life of the frequency converter is reduced if derating for ambient temperature is not taken into account.
 
5.1.5 Field Mounting
For field mounting the IP 21/IP 4X top/TYPE 1 kits or IP 54/55 units are recommended.