6.1.5 Smart Logic Control Programming
New useful facility in VLT AQUA Drive is the Smart Logic Control (SLC).
In applications where a PLC is generating a simple sequence the SLC may take over elementary tasks from the main control.
SLC is designed to act from event send to or generated in the VLT AQUA Drive . The frequency converter will then perform the pre-programmed action.
6.1.6 SLC Application Example
One sequence 1:
Start – ramp up – run at reference speed 2 sec – ramp down and hold shaft until stop.
Set the ramping times in par. 3-41
Ramp 1 Ramp Up Time
and par. 3-42
Ramp 1 Ramp Down Time
to the wanted times
t
ramp
=
t
acc
×
n
norm
(
par
. 1 25
)
ref
RPM
Set term 27 to
No Operation
(par. 5-12
Terminal 27 Digital Input
)
Set Preset reference 0 to first preset speed (par. 3-10
Preset Reference
[0]) in percentage of Max reference speed (par. 3-03
Maximum Reference
). Ex.:
60%
Set preset reference 1 to second preset speed (par. 3-10
Preset Reference
[1] Ex.: 0 % (zero).
VLT
®
AQUA Drive Design Guide 6 Application Examples
MG.20.N5.02 - VLT
®
is a registered Danfoss trademark
161
6

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive Series and is the answer not in the manual?

Danfoss VLT AQUA Drive Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive Series
CategoryMedia Converter
LanguageEnglish

Related product manuals