Frequency converter: Max. fuse size: Voltage: Type:
200-240 V
K25-K75
10A
1
200-240 V type gG
1K1-2K2
20A
1
200-240 V type gG
3K0
30A
1
200-240 V type gG
3K7
30A
1
200-240 V type gG
5K5
50A
1
200-240 V type gG
7K5
63A
1
200-240 V type gG
11K
63A
1
200-240 V type gG
15K
80A
1
200-240 V type gG
18K5
125A
1
200-240 V type gG
22K
125A
1
200-240 V type gG
30K
160A
1
200-240 V type gG
37K
200A
1
200-240 V type aR
45K
250A
1
200-240 V type aR
380-480 V
K37-1K5
10A
1
380-480 V type gG
2K2-4K0
20A
1
380-480 V type gG
5K5-7K5
30A
1
380-480 V type gG
11K
63A
1
380-480 V type gG
15K
63A
1
380-480 V type gG
18K
63A
1
380-480 V type gG
22K
63A
1
380-480 V type gG
30K
80A
1
380-480 V type gG
37K
100A
1
380-480 V type gG
45K
125A
1
380-480 V type gG
55K
160A
1
380-480 V type gG
75K
250A
1
380-480 V type aR
90K
250A
1
380-480 V type aR
Table 5.4: Non UL fuses 200 V to 480 V
1) Max. fuses - see national/international regulations for selecting an applicable fuse size.
Danfoss PN
Bussmann Ferraz Siba
20220 170M4017 6.9URD31D08A0700 20 610 32.700
20221 170M6013 6.9URD33D08A0900 20 630 32.900
Table 5.5: Additional Fuses for Non-UL Applications, E enclosures, 380-480 V
UL Compliance
VLT AQUA
Bussmann Bussmann Bussmann SIBA Littel fuse
Ferraz-
Shawmut
Ferraz-
Shawmut
200-240 V
kW
Type RK1 Type J Type T Type RK1 Type RK1 Type CC Type RK1
K25-1K1 KTN-R10 JKS-10 JJN-10 5017906-010 KLN-R10 ATM-R10 A2K-10R
1K5 KTN-R15 JKS-15 JJN-15 5017906-015 KLN-R15 ATM-R15 A2K-15R
2K2 KTN-R20 JKS-20 JJN-20 5012406-020 KLN-R20 ATM-R20 A2K-20R
3K0 KTN-R25 JKS-25 JJN-25 5012406-025 KLN-R25 ATM-R25 A2K-25R
3K7 KTN-R30 JKS-30 JJN-30 5012406-030 KLN-R30 ATM-R30 A2K-30R
5K5 KTN-R50 JKS-50 JJN-50 5012406-050 KLN-R50 - A2K-50R
7K5 KTN-R50 JKS-60 JJN-60 5012406-050 KLN-R60 - A2K-50R
11K KTN-R60 JKS-60 JJN-60 5014006-063 KLN-R60 A2K-60R
15K KTN-R80 JKS-80 JJN-80 5014006-080 KLN-R80 A2K-80R
18K5 KTN-R125 JKS-150 JJN-125 2028220-125 KLN-R125 A2K-125R
22K KTN-R125 JKS-150 JJN-125 2028220-125 KLN-R125 A2K-125R
30K FWX-150 - - 2028220-150 L25S-150 A25X-150
37K FWX-200 - - 2028220-200 L25S-200 A25X-200
45K FWX-250 - - 2028220-250 L25S-250 A25X-250
Table 5.7: UL fuses 200 - 240 V
5 How to Install VLT
®