Normal overload 110% for 1 minute
IP 20 / NEMA Chassis A2 A2 A2 A2 A2 A2 A2 A3 A3
IP 21 / NEMA 1 A2 A2 A2 A2 A2 A2 A2 A3 A3
IP 55 / NEMA 12 A5 A5 A5 A5 A5 A5 A5 A5 A5
IP 66
A5 A5 A5 A5 A5 A5 A5 A5 A5
Mains supply 200 - 240 VAC
Frequency converter
Typical Shaft Output [kW]
PK25
0.25
PK37
0.37
PK55
0.55
PK75
0.75
P1K1
1.1
P1K5
1.5
P2K2
2.2
P3K0
3
P3K7
3.7
Typical Shaft Output [HP] at 208 V 0.25 0.37 0.55 0.75 1.5 2.0 2.9 4.0 4.9
Output current
Continuous
(3 x 200-240 V ) [A]
1.8 2.4 3.5 4.6 6.6 7.5 10.6 12.5 16.7
Intermittent
(3 x 200-240 V ) [A]
1.98 2.64 3.85 5.06 7.26 8.3 11.7 13.8 18.4
Continuous
kVA (208 V AC) [kVA]
0.65 0.86 1.26 1.66 2.38 2.70 3.82 4.50 6.00
Max. cable size:
(mains, motor, brake)
[mm
2
/AWG]
2)
0.2 - 4 mm
2
/ 4 - 10 AWG
Max. input current
Continuous
(3 x 200-240 V ) [A]
1.6 2.2 3.2 4.1 5.9 6.8 9.5 11.3 15.0
Intermittent
(3 x 200-240 V ) [A]
1.7 2.42 3.52 4.51 6.5 7.5 10.5 12.4 16.5
Max. pre-fuses
1)
[A]
10 10 10 10 20 20 20 32 32
Environment
Estimated power loss
at rated max. load [W]
4)
21 29 42 54 63 82 116 155 185
Weight enclosure IP20 [kg] 4.9 4.9 4.9 4.9 4.9 4.9 4.9 6.6 6.6
Weight enclosure IP21 [kg] 5.5 5.5 5.5 5.5 5.5 5.5 5.5 7.5 7.5
Weight enclosure IP55 [kg] 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5
Weight enclosure IP 66 [kg] 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5
Efficiency
3)
0.94 0.94 0.95 0.95 0.96 0.96 0.96 0.96 0.96
3.1.2 Mains Supply 3 x 200 - 240 VAC
VLT
®
AQUA Drive Design Guide 3 VLT AQUA Selection
MG.20.N5.02 - VLT
®
is a registered Danfoss trademark
41