Mains Supply 1x 380 VAC - Normal overload 110% for 1 minute
Frequency converter
Typical Shaft Output [kW]
P7K5
7.5
P11K
11
P18K
18.5
P37K
37
Typical Shaft Output [HP] at 460 V 10 15 25 50
IP 21 / NEMA 1 B1 B2 C1 C2
IP 55 / NEMA 12 B1 B2 C1 C2
IP 66
B1 B2 C1 C2
Output current
Continuous
(3 x 380-440 V) [A]
16 24 37.5 73
Intermittent
(3 x 380-440 V) [A]
17.6 26.4 41.2 80.3
Continuous
(3 x 441-480 V) [A]
14.5 21 34 65
Intermittent
(3 x 441-480 V) [A]
15.4 23.1 37.4 71.5
Continuous kVA
(400 V AC) [kVA]
11.0 16.6 26 50.6
Continuous kVA
(460 V AC) [kVA]
11.6 16.7 27.1 51.8
Max. cable size:
(mains, motor, brake)
[[mm
2
/ AWG]
2)
10/7 35/2 50/1/0 120/4/0
Max. input current
Continuous
(1 x 380-440 V ) [A]
33 48 78 151
Intermittent
(1 x 380-440 V ) [A]
36 53 85.8 166
Continuous
(1 x 441-480 V) [A]
30 41 72 135
Intermittent
(1 x 441-480 V) [A]
33 46 79.2 148
Max. pre-fuses
1)
[A]
63 80 160 250
Environment
Estimated power loss
at rated max. load [W]
4)
300 440 740 1480
Weight enclosure IP 21 [kg] 23 27 45 65
Weight enclosure IP 55 [kg] 23 27 45 65
Weight enclosure IP 66 [kg] 23 27 45 65
Efficiency
3)
0.96 0.96 0.96 0.96
3.1.3 Mains Supply 1 x 380 - 480 VAC
VLT
®
AQUA Drive Design Guide 3 VLT AQUA Selection
MG.20.N5.02 - VLT
®
is a registered Danfoss trademark
43
3