Normal overload 110% for 1 minute
Frequency converter
Typical Shaft Output [kW] at 400V
P110
110
P132
132
P160
160
P200
200
P250
250
315
P400
400
P450
450
P500
500
P560
560
P630
630
P710
710
P800
800
P1M0
1000
Typical Shaft Output [HP] at 460V 150 200 250 300 350 450 550 600 650 750 900 1000 1200 1350
IP 00 D3 D3 D4 D4 D4 E2 E2 E2 F1/F3 F1/F3 F1/F3 F1/F3 F2/F4 F2/F4
IP 21 / Nema 1 D1 D1 D2 D2 D2 E1 E1 E1 F1/F3 F1/F3 F1/F3 F1/F3 F2/F4 F2/F4
IP 54 / Nema 12 D1 D1 D2 D2 D2 E1 E1 E1 F1/F3 F1/F3 F1/F3 F1/F3 F2/F4 F2/F4
Output current
Continuous (3 x 380-440 V) [A] 212 260 315 395 480 600 745 800 880 990 1120 1260 1460 1720
Intermittent (3 x 380-440 V) [A] 233 286 347 435 528 660 820 880 968 1089 1232 1386 1606 1892
Continuous (3 x 441-480V) [A] 190 240 302 361 443 540 678 730 780 890 1050 1160 1380 1530
Intermittent (3 x 441-480V) [A] 209 264
332 397 487 594 746 803 858 979 1155 1276 1518 1683
Continuous kVA (400 VAC) [kVA] 147 180 218 274 333 416 516 554 610 686 776 873 1012 1192
Continuous kVA (460 VAC) [kVA]
151 191 241 288 353 430 540 582 621 709 837 924 1100 1219
Max. cable size:
( motor,) [mm
2
/ AWG
2)
]
2x70
2x2/0
2x185
2x300 mcm
4x240
4x500 mcm
8x150
8x300 mcm
12x150
12x300 mcm
(mains, ) [mm
2
/ AWG
2)
]
2x70
2x2/0
2x185
2x300 mcm
4x240
4x500 mcm
8x240
8x500 mcm
(loadsharing) [mm
2
/ AWG
2)
]
2x70
2x2/0
2x185
2x300 mcm
4x240
4x500 mcm
4x120
4x250 mcm
( brake) [mm
2
/ AWG
2)
]
2x70
2x2/0
2x185
2x300 mcm
2x185
2x350 mcm
4x185
4x350 mcm
6x185
6x350 mcm
Max. input current
Continuous (3 x 380-440 V) [A] 204 251 304 381 463 590 733 787 857 964 1090 1227 1422 1675
Continuous (3 x 441-480V) [A] 183 231 291 348 427 531 667 718 759 867 1022 1129 1344 1490
Max. pre-fuses
1)
[A]
300 350 400 500 630 700 900 900 1600 1600 2000 2000 2500 2500
Environment:
Estimated power loss at 400 VAC
at rated max. load [W]
4)
3234 3782 4213 5119 5893 6790 8879 9670 10647 12338 13201 15436 18084 20358
Estimated power loss at 460 VAC
at rated max. load [W]
4)
2947 3665 4063 4652 5634 6082 8089 8803 9414 11006 12353 14041 17137 17752
Weight enclosure IP00 [kg] 82 91 112 123 138 221 236 277 - - - - - -
Weight enclosure IP 21 [kg] 96 104
125 136 151 263 272 313 1004 1004 1004 1004 1246 1246
Weight enclosure IP 54 [kg] 96 104 125 136 151 263 272 313 1299 1299 1299 1299 1541 1541
Efficiency
3)
0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98
1)
For type of fuse see section
Fuses
2)
American Wire Gauge
3)
Measured using 5 m screened motor cables at rated load and rated frequency
4)
The typical power loss is at normal load conditions and expected to be within +/- 15% (tolerance relates to variety in voltage and cable conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line). Lower efficiency motors will also add to the power loss in the frequency converter and vice versa.
If the switching frequency is raised from nominal the power losses may rise significantly.
LCP and typical control card power consumptions are included. Further options and customer load may add up to 30 Watts to the losses. (Though typically only 4 Watts extra for a fully loaded control card or options for slot A or
slot B, each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/- 5%).
3 VLT AQUA Selection VLT
®
AQUA Drive Design Guide
46