Normal overload 110% for 1 minute
Size: P11K P15K P18K P22K P30K P37K P45K P55K P75K P90K
Typical Shaft Output [kW] 11 15 18.5 22 30 37 45 55 75 90
Typical Shaft Output [HP] at 575 V 10 16.4 20.1 24 33 40 50 60 75 100
IP 21 / NEMA 1 B2B2B2B2B2
C2 C2 C2 C2 C2
IP 55 / NEMA 12 B2 B2 B2 B2 B2 C2 C2 C2 C2 C2
Output current
Continuous
(3 x 525-550 V ) [A]
14 19 23 28 36 43 54 65 87 105
Intermittent
(3 x 525-550 V ) [A]
15.4 20.9 25.3 30.8 39.6
47.3 59.4 71.5 95.7 115.5
Continuous
(3 x 551-690 V ) [A]
13 18 22 27 34 41 52 62 83 100
Intermittent
(3 x 551-690 V ) [A]
14.3 19.8 24.2 29.7 37.4
45.1 57.2 68.2 91.3 110
Continuous kVA (550 V AC) [kVA] 13.3 18.1 21.9 26.7 34.3 41 51.4 61.9 82.9 100
Continuous kVA (575 V AC) [kVA] 12.9 17.9 21.9 26.9 33.8
40.8 51.8 61.7 82.7 99.6
Continuous kVA (690 V AC) [kVA]
15.5
21.5 26.3 32.3
40.6 49
62.1 74.1 99.2 119.5
Max. cable size
(mains, motor, brake)
[mm
2
]/[AWG]
2)
35
1/0
95
4/0
Max. input current
Continuous
(3 x 525-690 V ) [A]
15 19.5 24 29 36 49 59 71 87 99
Intermittent
(3 x 525-690 V ) [A]
16.5 21.5 26.4 31.9 39.6 53.9 64.9 78.1 95.7 108.9
Max. pre-fuses
1)
[A]
60 60 60 60 60
150 150 150 150 150
Environment:
Estimated power loss
at rated max. load [W]
4)
201 285 335 375 430 592 720 880 1200 1440
Weight:
IP21 [kg] 27 27 27 27 27
65 65 65 65 65
IP55 [kg] 27 27 27 27 27 65 65 65 65 65
Efficiency
4)
0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98
Table 3.2:
5)
Motor and mains cable: 300MCM/150mm