A2, A3 and B3 enclosures A5, B1, B2, B4, C1, C2, C3 and C4 enclosures
3.6.2 General Purpose Input Output Module MCB 101
MCB 101 is used for extension of the number of digital and analog inputs
and outputs of the VLT AQUA Drive.
Contents: MCB 101 must be fitted into slot B in the VLT AQUA
Drive.
MCB 101 option module
•Extended LCP frame
Terminal cover
Galvanic Isolation in the MCB 101
Digital/analog inputs are galvanically isolated from other inputs/outputs on the MCB 101 and in the control card of the drive. Digital/analog outputs in
the MCB 101 are galvanically isolated from other inputs/outputs on the MCB 101, but not from these on the control card of the drive.
If the digital inputs 7, 8 or 9 are to be switched by use of the internal 24 V power supply (terminal 9) the connection between terminal 1 and 5 which is
illustrated in the drawing has to be established.