Illustration 3.23: Principle diagram for Analog I/O mounted in frequency converter.
Analog I/O configuration
3 x Analog Inputs, capable of handling following:
0 - 10 VDC
OR
0-20 mA (voltage input 0-10V) by mounting a 510 resistor across terminals (see NB!)
4-20 mA (voltage input 2-10V) by mounting a 510 resistor across terminals (see NB)
Ni1000 temperature sensor of 1000 at 0° C. Specifications according to DIN43760
Pt1000 temperature sensor of 1000 at 0° C. Specifications according to IEC 60751
3 x Analog Outputs supplying 0-10 VDC.
NB!
Please note the values available within the different standard groups of resistors:
E12: Closest standard value is 470, creating an input of 449.9 and 8.997V.
E24: Closest standard value is 510, creating an input of 486.4 and 9.728V.
E48: Closest standard value is 511, creating an input of 487.3 and 9.746V.
E96: Closest standard value is 523, creating an input of 498.2 and 9.964V.
Analog inputs - terminal X42/1-6
Parameter group for read out: 18-3*. See also
Programming Guide.
Parameter groups for set-up: 26-0*, 26-1*, 26-2* and 26-3*. See also
Programming Guide.