EasyManuals Logo

Danfoss VLT AQUA Drive Series User Manual

Danfoss VLT AQUA Drive Series
204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #73 background imageLoading...
Page #73 background image
Illustration 3.23: Principle diagram for Analog I/O mounted in frequency converter.
Analog I/O configuration
3 x Analog Inputs, capable of handling following:
0 - 10 VDC
OR
0-20 mA (voltage input 0-10V) by mounting a 510 resistor across terminals (see NB!)
4-20 mA (voltage input 2-10V) by mounting a 510 resistor across terminals (see NB)
Ni1000 temperature sensor of 1000 at 0° C. Specifications according to DIN43760
Pt1000 temperature sensor of 1000 at 0° C. Specifications according to IEC 60751
3 x Analog Outputs supplying 0-10 VDC.
NB!
Please note the values available within the different standard groups of resistors:
E12: Closest standard value is 470, creating an input of 449.9 and 8.997V.
E24: Closest standard value is 510, creating an input of 486.4 and 9.728V.
E48: Closest standard value is 511, creating an input of 487.3 and 9.746V.
E96: Closest standard value is 523, creating an input of 498.2 and 9.964V.
Analog inputs - terminal X42/1-6
Parameter group for read out: 18-3*. See also
Programming Guide.
Parameter groups for set-up: 26-0*, 26-1*, 26-2* and 26-3*. See also
Programming Guide.
VLT
®
AQUA Drive Design Guide 3 VLT AQUA Selection
MG.20.N5.02 - VLT
®
is a registered Danfoss trademark
73
3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive Series and is the answer not in the manual?

Danfoss VLT AQUA Drive Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive Series
CategoryMedia Converter
LanguageEnglish

Related product manuals