5.3.24 29-** Water Application Functions
Par.
No. #
Parameter description Default value 4-set-up Change dur-
ing operation
Conver-
sion index
Type
29-0* Pipe Fill
29-00 Pipe Fill Enable [0] Disabled 2 set-ups FALSE - Uint8
29-01 Pipe Fill Speed [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
29-02 Pipe Fill Speed [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
29-03 Pipe Fill Time 0.00 s All set-ups TRUE -2 Uint32
29-04 Pipe Fill Rate 0.001 ProcessCtrlUnit All set-ups TRUE -3 Int32
29-05 Filled Setpoint 0.000 ProcessCtrlUnit All set-ups TRUE -3 Int32
5.3.25 31-** Bypass Option
Par.
No. #
Parameter description Default value 4-set-up Change dur-
ing operation
Conver-
sion index
Type
31-00 Bypass Mode [0] Drive All set-ups TRUE - Uint8
31-01 Bypass Start Time Delay 30 s All set-ups TRUE 0 Uint16
31-02 Bypass Trip Time Delay 0 s All set-ups TRUE 0 Uint16
31-03 Test Mode Activation [0] Disabled All set-ups TRUE - Uint8
31-10 Bypass Status Word 0 N/A All set-ups FALSE 0 V2
31-11 Bypass Running Hours 0 h All set-ups FALSE 74 Uint32
31-19 Remote Bypass Activation [0] Disabled 2 set-ups TRUE - Uint8
5 How to program the adjustable frequency
drive
VLT AQUA High Power Instruction Manual
5-68
MG.20.P3.22 - VLT
®