3.6.22 Electrical Installation, Control Terminals
To connect the cable to the terminal:
1. Strip insulation by about 0.34–0.39 in [9–10 mm]
2.
Insert a screwdriver
1)
in the square hole.
3. Insert the cable in the adjacent circular hole.
4. Remove the screwdriver. The cable is now mounted in the terminal.
To remove the cable from the terminal:
1.
Insert a screwdriver
1)
in the square hole.
2. Pull out the cable.
1)
Max. 0.015 x 0.1 in. [0.4 x 2.5 mm]
1.
2.
3.
3 How to Install VLT AQUA High Power Instruction Manual
3-66
MG.20.P3.22 - VLT
®
is a registered Danfoss trademark