3.9 Final Set-up and Test
To test the set-up and ensure that the adjustable frequency drive is running, follow these steps.
Step 1. Locate the motor nameplate
NOTE!
The motor is either star- (Y) or delta-connected (). This information is located on the motor nameplate data.
Step 2. Enter the motor nameplate data in this parameter list.
To access this list, first press the [QUICK MENU] key, then select “Q2
Quick Set-up”.
1. par. 1-20
Motor Power [kW]
par. 1-21
Motor Power [HP]
2. par. 1-22
Motor Voltage
3. par. 1-23
Motor Frequency
4. par. 1-24
Motor Current
5. par. 1-25
Motor Nominal Speed
VLT AQUA High Power Instruction Manual 3 How to Install
MG.20.P3.22 - VLT
®
is a registered Danfoss trademark
3-73
3