2.1.8 Safe Stop of the Adjustable Frequency Drive
For versions fitted with a Safe Stop terminal 37 input, the adjustable frequency drive can perform the safety function
Safe Torque Off
(As defined by
draft CD IEC 61800-5-2) or
Stop Category 0
(as defined in EN 60204-1).
It is designed and approved suitable for the requirements of Safety Category 3 in EN 954-1. This functionality is called Safe Stop. Prior to integration and
use of Safe Stop in an installation, a thorough risk analysis on the installation must be carried out in order to determine whether the Safe Stop functionality
and safety category are appropriate and sufficient. In order to install and use the Safe Stop function in accordance with the requirements of Safety
Category 3 in EN 954-1, the related information and instructions of the VLT AQUA Drive Design Guide MG.20.NX.YY must be followed! The information
and instructions of the Instruction Manual are not sufficient for a correct and safe use of the Safe Stop functionality!
VLT AQUA High Power Instruction Manual 2 Safety
MG.20.P3.22 - VLT
®
is a registered Danfoss trademark
2-5
2

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
BrandDanfoss
Modelvlt aqua
CategoryDC Drives
LanguageEnglish

Related product manuals