EasyManuals Logo

Danfoss vlt aqua User Manual

Danfoss vlt aqua
205 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #157 background imageLoading...
Page #157 background image
5.3.3 1-** Load/Motor
Par.
No. #
Parameter description Default value 4-set-up Change dur-
ing operation
Conver-
sion index
Type
1-0* General Settings
1-00 Configuration Mode null All set-ups TRUE - Uint8
1-01 Motor Control Principle null All set-ups FALSE - Uint8
1-03 Torque Characteristics [3] Auto Energy Optim. VT All set-ups TRUE - Uint8
1-1* Motor Selection
1-10 Motor Construction [0] Asynchronous All set-ups FALSE - Uint8
1-2* Motor Data
1-20 Motor Power [kW] ExpressionLimit All set-ups FALSE 1 Uint32
1-21 Motor Power [HP] ExpressionLimit All set-ups FALSE -2 Uint32
1-22 Motor Voltage ExpressionLimit All set-ups FALSE 0 Uint16
1-23 Motor Frequency ExpressionLimit All set-ups FALSE 0 Uint16
1-24 Motor Current ExpressionLimit All set-ups FALSE -2 Uint32
1-25 Motor Nominal Speed ExpressionLimit All set-ups FALSE 67 Uint16
1-28 Motor Rotation Check [0] OFF All set-ups FALSE - Uint8
1-29 Automatic Motor Adaptation (AMA) [0] Off All set-ups FALSE - Uint8
1-3* Addl. Motor Data
1-30 Stator Resistance (Rs) ExpressionLimit All set-ups FALSE -4 Uint32
1-31 Rotor Resistance (Rr) ExpressionLimit All set-ups FALSE -4 Uint32
1-32 Stator Reactance (Xs) ExpressionLimit All set-ups FALSE -4 Uint32
1-33 Stator Leakage Reactance (X1) ExpressionLimit All set-ups FALSE -4 Uint32
1-34 Rotor Leakage Reactance (X2) ExpressionLimit All set-ups FALSE -4 Uint32
1-35 Main Reactance (Xh) ExpressionLimit All set-ups FALSE -4 Uint32
1-36 Iron Loss Resistance (Rfe) ExpressionLimit All set-ups FALSE -3 Uint32
1-39 Motor Poles ExpressionLimit All set-ups FALSE 0 Uint8
1-5* Load-Indep. Setting
1-50 Motor Magnetization at Zero Speed 100 % All set-ups TRUE 0 Uint16
1-51 Min Speed Normal Magnetizing [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
1-52 Min Speed Normal Magnetizing [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
1-55 U/f Characteristic - U ExpressionLimit All set-ups TRUE -1 Uint16
1-56
U/f Characteristic - F ExpressionLimit All set-ups TRUE -1 Uint16
1-6* Load-Depend. Settg.
1-60 Low Speed Load Compensation 100 % All set-ups TRUE 0 Int16
1-61 High Speed Load Compensation 100 % All set-ups TRUE 0 Int16
1-62 Slip Compensation 0 % All set-ups TRUE 0 Int16
1-63 Slip Compensation Time Constant ExpressionLimit All set-ups TRUE -2 Uint16
1-64 Resonance Dampening 100 % All set-ups TRUE 0 Uint16
1-65 Resonance Dampening Time Constant 5 ms All set-ups TRUE -3 Uint8
1-7* Start Adjustments
1-71 Start Delay 0.0 s All set-ups TRUE -1 Uint16
1-73 Flying Start [0] Disabled All set-ups FALSE - Uint8
1-74 Start Speed [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
1-75 Start Speed [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
1-76 Start Current 0.00 A All set-ups TRUE -2 Uint32
5.3.4 2-** Brakes
Par.
No. #
Parameter description Default value 4-set-up Change dur-
ing operation
Conver-
sion index
Type
2-0* DC Brake
2-00 DC Hold/Preheat Current 50 % All set-ups TRUE 0 Uint8
2-01 DC Brake Current 50 % All set-ups TRUE 0 Uint16
2-02 DC Braking Time 10.0 s All set-ups TRUE -1 Uint16
2-03 DC Brake Cut-in Speed [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
2-04
DC Brake Cut-in Speed [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
2-1* Brake Energy Funct.
2-10 Brake Function [0] Off All set-ups TRUE - Uint8
2-11 Brake Resistor (ohm) ExpressionLimit All set-ups TRUE 0 Uint16
2-12 Brake Power Limit (kW) ExpressionLimit All set-ups TRUE 0 Uint32
2-13 Brake Power Monitoring [0] Off All set-ups TRUE - Uint8
2-15 Brake Check [0] Off All set-ups TRUE - Uint8
2-16 AC Brake Max. Current 100.0 % All set-ups TRUE -1 Uint32
2-17 Over-voltage Control [2] Enabled All set-ups TRUE - Uint8
VLT AQUA High Power Instruction Manual
5 How to program the adjustable frequency
drive
MG.20.P3.22 - VLT
®
is a registered Danfoss trademark
5-51
5

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled

Related product manuals