EasyManuals Logo
Home>Danfoss>DC Drives>VLT AutomationDrive FC 300 Series

Danfoss VLT AutomationDrive FC 300 Series User Manual

Danfoss VLT AutomationDrive FC 300 Series
206 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #184 background imageLoading...
Page #184 background image
Table 129: Non-fusible Disconnect Switches for VLT
®
AutomationDrive FC 302 Enclosed Drive Models N90K–N250, 525–690 V
N90K
N110
N132
N160
N200
N250
IEC
400 A/690 V
400 A/690 V
400 A/690 V
630 A/690 V
630 A/690 V
630 A/690 V
ABB P/N
OT400E30
OT400E30
OT400E30
OT630E30
OT630E30
OT630E30
UL
400 A/600 V
400 A/600 V
400 A/600 V
600 A/600 V
600 A/600 V
600 A/600 V
ABB P/N
OT400U30
OT400U30
OT400U30
OT600U30
OT600U30
OT600U30
Table 130: Non-fusible Disconnect Switches for VLT
®
AutomationDrive FC 302 Enclosed Drive Models N315–N560, 525–690 V
N315
N355
N400
N500
N560
IEC
630 A/690 V
630 A/690 V
630 A/690 V
1000 A/690 V
1000 A/690 V
ABB P/N
OT630E30
OT630E30
OT630E30
OT1000E30
OT1000E30
UL
600 A/600 V
600 A/600 V
600 A/600 V
800 A/600 V
800 A/600 V
ABB P/N
OT600U30
OT600U30
OT600U30
OT800U30
OT800U30
Table 131: Non-fusible Disconnect Switches for VLT
®
AutomationDrive FC 302 Enclosed Drive Models N630–N710, 525–690 V
N630
N710
IEC
1250 A/690 V
1250 A/690 V
ABB P/N
OT1250E30
OT1250E30
UL
1200 A/600 V
1200 A/600 V
ABB P/N
OT1200U30
OT1200U30
10.8.5 Molded-case Circuit Breakers
The molded-case circuit breaker (MCCB) is an option that combines a temperature-sensitive device with a current-sensitive electro-
magnetic device to protect the drive.
Table 132: MCCB Part Numbers for VLT
®
AutomationDrive FC 302 Enclosed Drive Models N90K–N250, 380–500 V
N90K
N110
N132
N160
N200
N250
IEC
400 A/690 V
400 A/690 V
400 A/690 V
800 A/690 V
800 A/690 V
800 A/690 V
ABB P/N
T5L400
T5L400
T5L400
T6L800
T6L800
T6L800
UL
400 A/600 V
400 A/600 V
400 A/600 V
600 A/600 V
600 A/600 V
800 A/600 V
ABB P/N
T5L400BW
T5L400BW
T5LQ400BW
T6L600BW
T6LQ600BW
T6LQ800BW
Table 133: MCCB Part Numbers for VLT
®
AutomationDrive FC 302 Enclosed Drive Models N315–N500, 380–500 V
N315
N355
N400
N450
N500
IEC
1000 A/690 V
1250 A/690 V
1250 A/690 V
1250 A/690 V
1600 A/690 V
ABB
P/N
T71000LSPR231 DS-
LS
T71250LSPR231 DS-
LS
T71250LSPR231 DS-LS
T71250LSPR231 DS-
LS
T71600LSPR231 DS-
LS
UL
1200 A/600 V
1200 A/600 V
1200 A/600 V
1600 A/600 V
1600 A/600 V
ABB
P/N
T7L1200PR231/P
T7L1200PR231/P
T7LQ1200PR231/P
T8V1600PR232/P
T8V1600PR232/P
AQ262139143212en-000301 / 130R0879184 | Danfoss A/S © 2021.10
Specifications
VLT® AutomationDrive FC 302
Operating Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 Series and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300 Series
CategoryDC Drives
LanguageEnglish

Related product manuals