FC 300 Design Guide
How to Program
Function:
Defines the action after receiving a valid control
word upon a timeout. This only applies if set-up
1-4 has been selected in par. 8-04.
Hold: The drive holds the set-up selected in par.
8-04 and displays a warning, until par. 8-06 toggles.
Then the drive resum es its original set-up.
Resume: The drive resumes the original set-up.
8-06 Reset Control Word Timeout
Option:
*
Do not reset [0]
Do reset [1]
Function:
Used for returning the drive to the original set-up
after a Control word timeout. W hen setting the value
to "Do Reset" [1], it returns to "Do not re set" [0].
8-07 Diagnosis Trigger
Option:
*
Disable [0]
Trigger on alarm s [1]
Trigger alarms/warn. [2]
Function:
Enables and controls the drive diagnostic
function and permits expa nsion of the
diagnostic data to 24 byte.
- Disable: Extended diagnostic data are
not sent even if they appear in the
adjustable frequency drive
- Trigger on alarms: Extended diagnostic data
are sent when one or more alarms appear
in alarm par. 16-04 or 9-53.
- Trigger alarms/warn: Extended diagnostic
data are sent if one or more alarms/warnings
appear in alarm par. 16-04, 9-53, or
warning p arameter 16-05.
The content of the ex tended diagnostic frame is as follows:
Byte Content Description
0-5 Standard DP
Diagnostic Data
Standard DP Diagnostic Data
6 PDU length xx Header of extended diagnostic
data
7 Status type =
0x81
Header of extended diagnostic
data
8 Slot = 0 Header of extended diagnostic
data
9 Status info = 0 Header of extended diagnostic
data
10 - 13 VLT par. 16-05 VLT warning word
14 - 17 VLT par. 16-06 VLT status word
18 - 21 VLT par. 16-04 VLT alarm word
22 - 23 VLT par. 9-53 Communication warning w ord
(Profibus)
Enabling diagnostics may cause increased
bus traffic. Diagnostic functions are not
supported by all fieldbus types.
" 8-1* Ctrl. Word Settings
8-10 Control Word Profile
Option:
*
FC profile [0]
PROFIdrive profile [1]
ODVA [5]
CANopen [7]
Function:
Selects the interp retation of the control and
status words. The installed option in slot A
determines the valid selection.
" 8-3* FC Port Settings
8-30 Protocol
Option:
*
FC [0]
FC M C [1]
Function:
Protocol selection for the FC (standard) port.
8-31 Address
Range:
1-126
*
1
*
default setting ()display text []value for use in communication via serial communication port
183