FC 300 Design Guide
How to Program
Function:
Defines the action after receiving a valid control
word upon a timeout. This only applies if set-up
1-4 has been selected in par. 8-04.
Hold: The drive holds the set-up selected in par.
8-04 and displays a warning, until par. 8-06 toggles.
Then the drive resum es its original set-up.
Resume: The drive resumes the original set-up.
8-06 Reset Control Word Timeout
Option:
*
Do not reset [0]
Do reset [1]
Function:
Used for returning the drive to the original set-up
after a Control word timeout. W hen setting the value
to "Do Reset" [1], it returns to "Do not re set" [0].
8-07 Diagnosis Trigger
Option:
*
Disable [0]
Trigger on alarm s [1]
Trigger alarms/warn. [2]
Function:
Enables and controls the drive diagnostic
function and permits expa nsion of the
diagnostic data to 24 byte.
- Disable: Extended diagnostic data are
not sent even if they appear in the
adjustable frequency drive
- Trigger on alarms: Extended diagnostic data
are sent when one or more alarms appear
in alarm par. 16-04 or 9-53.
- Trigger alarms/warn: Extended diagnostic
data are sent if one or more alarms/warnings
appear in alarm par. 16-04, 9-53, or
warning p arameter 16-05.
The content of the ex tended diagnostic frame is as follows:
Byte Content Description
0-5 Standard DP
Diagnostic Data
Standard DP Diagnostic Data
6 PDU length xx Header of extended diagnostic
data
7 Status type =
0x81
Header of extended diagnostic
data
8 Slot = 0 Header of extended diagnostic
data
9 Status info = 0 Header of extended diagnostic
data
10 - 13 VLT par. 16-05 VLT warning word
14 - 17 VLT par. 16-06 VLT status word
18 - 21 VLT par. 16-04 VLT alarm word
22 - 23 VLT par. 9-53 Communication warning w ord
(Profibus)
Enabling diagnostics may cause increased
bus traffic. Diagnostic functions are not
supported by all fieldbus types.
" 8-1* Ctrl. Word Settings
8-10 Control Word Profile
Option:
*
FC profile [0]
PROFIdrive profile [1]
ODVA [5]
CANopen [7]
Function:
Selects the interp retation of the control and
status words. The installed option in slot A
determines the valid selection.
" 8-3* FC Port Settings
8-30 Protocol
Option:
*
FC [0]
FC M C [1]
Function:
Protocol selection for the FC (standard) port.
8-31 Address
Range:
1-126
*
1
*
default setting ()display text []value for use in communication via serial communication port
183
MG.33.B
3.22 - VLT is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals